Read/write function blocks
85
09/10 MN05013007Z-EN
Example
The master initiates the command for reading timing relay
T1:
The slave responds with the following values:
Value Set time = 0E10
hex
= 3600
3600 s = 60:00 M:S
Byte
Meaning
Valu
e
(hex)
Bit
7
6 5 4 3 2 1 0
0
Attribute ID: T1
2B
0
0 1 0 1 0 1 1
1 – 3
00
Byte
Meaning
Valu
e
(hex)
Bit
7 6 5 4 3 2 1 0
0
Response:
Read successful
C2
1 1 0 0 0 0 1 0
1
Trigger coil
activated,
M:S time base, on-
delayed, Parameter
d
l
1 0 0 0 1 0 0 0
2
Time actual value
(low byte)
10
0 0 0 1 0 0 0 0
3
Time actual value
(high byte)
0E
0 0 0 0 1 1 1 0
Содержание EASY222-DN