easy800/MFD control
commands
204
09/10 MN05013007Z-EN
Table 117:
Index 0 – Bit IO
Table 118:
Index 1 - Mode
Bit 7 6 5 4
3
2
1
0
FB input Data 1
– – – SE
1)
ED
2)
EI
3)
EP
4)
EN
5)
FB output Data 3
– – – –
–
–
–
LI
6)
1) Transfer of manual manipulated variable on status 1
2) Activation of D component on status 1
3) Activation of I component on status 1
4) Activation of P component on status 1
5) Activates the function block on status 1.
6) Status 1 if the value range of the medium-voltage was exceeded
Data 1
Operating Mode
UNP
unipolar
The manipulated variable is output as a unipolar
12-bit value. Corresponding value range for QV
0 to 4095.
BIP
bipolar
The manipulated variable is output as a bipolar
13-bit value. Corresponding value range for QV
–4096 to 4095
Содержание EASY222-DN
Страница 10: ...Contents 6 09 10 MN05013007Z EN...
Страница 34: ...30 09 10 MN05013007Z EN...
Страница 258: ...254 09 10 MN05013007Z EN...
Страница 274: ...Glossary 270 09 10 MN05013007Z EN...
Страница 284: ...Alphabetical index 09 10 MN05013007Z EN 280...