Read/write function block data
127
09/10 MN05013007Z-EN
Analog value comparator/threshold comparator:
A1 – A16
Telegram structure
Byte
Meaning
Value (hex), sent by
Master
Slave
Master
Slave
Attribute ID
Read
89
–
Write
8D
–
0
Response:
Read successful
–
C2
Write successful
–
C1
Command
rejected
–
C0
1)
0
1
Part no.
8D
8D
1
2
Instance
2
00 – 0F
00 – 0F
2
3
Index
3 – 6
4 – 7
Data 1 – 4
depending on
index,
depending on
index,
1) Possible causes
2) easy provides 16 analog comparators A1 to A16 for use as required. These can be
addressed using the instance (0 – F).