EATON Diesel Plus

O & M Manual IM05805019K

Diesel Engine Fire Pump Controller

Effective June 2011

EATON CORPORATION

 www.ceaton.com

3

1. INTRODUCTION

1.1 Safety

This technical document is intended to cover most aspects 
associated with the installation, application, operation, and 
maintenance of the Diesel Plus Fire Pump Controller. It is 
provided as a guide for authorized and qualified personnel only 
in the selection and application of the Diesel Plus Controller. If 
further information is required by the purchaser regarding 
particular installation, application, or maintenance activity, 
please contact an authorized EATON sales agent or the 
installing contractor.

1.2 Warranty

No warranties, expressed or implied, including warranties of 
fitness for a particular purpose of merchantability, or warranties 
arising from course of dealing or usage of trade, are made 
regarding the information, recommendations and descriptions 
contained herein. In no event will EATON be responsible to the 
purchaser or user in contract, in tort (including negligence), 
strict liability or otherwise for any special, indirect, incidental or 
consequential damage or loss whatsoever, including but not 
limited to damage or loss of use of equipment, plant or power 
system, cost of capital, loss of power, additional expenses in 
the use of existing power facilities, or claims against the 
purchaser of user by its customers resulting from the use of the 
information and descriptions contained herein.

1.3 Safety Precautions

All safety codes, safety standards, and/or regulations must be 
strictly observed in the installation, operation, and maintenance 
of this device.

CAUTION

COMPLETELY READ AND UNDERSTAND THE MATERIAL PRESENTED IN 
THIS DOCUMENT BEFORE ATTEMPTING INSTALLATION, OPERATION, OR 
APPLICATION OF THE EQUIPMENT. IN ADDITION, ONLY QUALIFIED 
PERSONS SHOULD BE PERMITTED TO PERFORM ANY WORK ASSOCIATED 
WITH THIS EQUIPMENT. ANY WIRING INSTRUCTIONS PRESENTED IN 
THIS DOCUMENT MUST BE FOLLOWED PRECISELY. FAILURE TO DO SO 
COULD CAUSE PERMANENT EQUIPMENT DAMAGE. 

1.4 Product Overview

The Diesel Plus Controller is a comprehensive, multi-function 
microprocessor based Fire Pump Controller.

Designed to meet the needs of markets worldwide, the Diesel 
Plus controller is certified by the following authorities: 
Underwrites Laboratories (UL), Underwriters Laboratories of 
Canada (ULC), Factory Mutual (FM), Canadian Standards 
Association (CSA), New York Department of Buildings (NYSB), 
and meet CE and U.B.C. / C.B.C. Seismic approval requirements.

2. INSTALLATION AND ELECTRICAL 

CONNECTIONS

2.1 Mounting

Carefully unpack the controller and inspect thoroughly.

The Diesel Plus controller is designed for either wall or floor 
mounting. Note that the controller is not free standing and must 
be mounted with feet or bolted securely to a wall. For 
dimensional and weight data please refer to the respective data 
sheets for the various types of Diesel Engine Fire Pump 
Controllers.

2.2 Pressure Sensor Connections

The Diesel Plus is equipped with a pressure sensor. The 
controller is provided with a 1/4" NPT female system pressure 
connection located on the bottom, external side of the 
enclosure. The connection should be installed as per NFPA, 20.

The pressure sensor and internal plumbing components are 
rated for a maximum of 500 PSI.

2.3 Electrical Connections

NOTICE

ALL CONDUIT CONNECTIONS TO THE CONTROLLER ARE RECOMMENDED 
TO BE INSTALLED ON THE BOTTOM OR LOWER RIGHT SIDE OF THE 
CONTROLLER. REFER TO THE ASSOCIATED DIMENSIONAL DRAWING FOR 
REFERENCE. DRILLING OR INSTALLING CONDUIT ABOVE THE 
MICROPROCESSOR BOARDS WILL VOID WARRANTY.

All electrical connections should meet national and local 
electrical codes and standards.

The controller should be located or so protected that it will not 
be damaged by water escaping from pumps or pump 
connections. Current carrying parts of controllers shall be a 
minimum of 12 inches (305 mm) above the floor.

Prior to starting, verify all data on the nameplate such as: 
catalog number and AC line voltage.

Inspect all electrical connections, components, and wiring for 
any visible damage. Correct as necessary. Ensure that all 
electrical connections are tightened before energization.

Refer to the appropriate field connection drawing affixed to the 
enclosure door, for all wiring information pertaining to the 
incoming AC power supply, batteries and engine wiring.

Terminals 1 through 12, 301 and 302, located on the lower 
terminal block, are for interconnection to the respective 
terminals on the diesel engine terminal block.

Incoming AC line voltage is clearly marked L, N and G (ground) 
located on the lower terminal block.

Install necessary conduit using proper methods and tools.

Terminals 11 through 34, located on the customer connections 
side of the I/O board are for connecting various input devices to 
the Diesel Plus. The customer Input terminals on the I/O board 
are designed to be used with dry (voltage free) contacts.

Содержание Diesel Plus 4A55737H01

Страница 1: ...Powering Business Worldwide EATON Diesel Plus Diesel Engine Fire Pump Controller O M Manual IM05805019K Effective June 2011...

Страница 2: ...2 Control Input Descriptions 9 4 3 3 Loss of DC Power 9 4 3 4 Speed Switch Malfunction 9 4 3 5 Engine Starter Coil Failure 9 4 3 6 Audible Alarm Silencing 9 4 3 7 Power Failure Alarm 10 4 4 Output Re...

Страница 3: ...utual FM Canadian Standards Association CSA New York Department of Buildings NYSB and meet CE and U B C C B C Seismic approval requirements 2 INSTALLATION AND EL ECTRICAL CONNECTIONS 2 1 Mounting Care...

Страница 4: ...y electronic and will protect itself by shutting down during a short circuit condition The maximum current draw that the chargers will draw when operating at 100 charging rate is 12 Volt System 24 Vol...

Страница 5: ...ttery charger cycle with NiCad batteries set DIP switches 3 and 6 to the ON position and all other DIP switches to the OFF position 3 1 7 Forced Charging There is provision for the battery chargers to...

Страница 6: ...ng a start signal from special starting equipment This is a normally closed contact that is required to be opened to start A factory installed jumper wire must be removed to use these contacts Termina...

Страница 7: ...ter button will allow the user to enter exit the message history statistics and diagnostics When in the menu system the enter button will allow the user to change the programmed set points and navigat...

Страница 8: ...g the cranking sequence Once the engine is running the controller will stop all further cranking STOP Modes The Stop Mode is programmable for Auto Shutdown On or Off see Appendix C Note that the engin...

Страница 9: ...er is factory installed The jumper must be removed in order to utilize this optional input Pump Start Terminal 36 When this input is in the Connected state the Diesel Plus controller will initiate an...

Страница 10: ...er Fail To Start After 6 cranking attempts three attempts per battery the Fail To Start annunciator will illuminate Attention to the diesel and its associated equipment is required immediately High En...

Страница 11: ...l initiate a start sequence Pressure Stop Point The value programmed determines the pressure the system must reach before the controller will automatically stop the fire pump motor via the running per...

Страница 12: ...sed on either of two separate conditions the stop pressure point or when the engine has started to run If the RPT is programmed to start at the Stop Pressure the timer will start timing once the syste...

Страница 13: ...en Timer A timer can be programmed to delay the time before the alarm becomes active Default value is 0 seconds Range is 0 500 seconds The timer will reset if the input is removed before the time has...

Страница 14: ...r to Appendix L for common messages and their meaning Refer to Section 7 to save the message history to a USB storage device or to view the message history on the optional embedded webpage 6 2 Statist...

Страница 15: ...r on press the Data Print button The first selection is Save to USB Press the Ack Alarm button and the controller will save the information to the USB storage device There will be five 5 files saved t...

Страница 16: ...t is as follows MMDDYYHHMM Month Day Year Hour Minute If any value entered between 1 and 9 needs to be lead by a 0 For example January 1 2009 8 15AM needs to be entered as 0101090815 NOTE All cells ne...

Страница 17: ...aton com 17 APPENDIX A MAIN MENU TREE MENU PASSWORD LANGUAGE REGIONAL SETTINGS PRESSURE SETTINGS TIMER VALUES CUSTOM INPUT OUTPUT SYSTEM CONFIG MENU MAIN MENU PASSWORD ACK ACK SELECT LANGUAGE ACK GO T...

Страница 18: ...p Controller 18 EATON CORPORATION www eaton com APPENDIX B REGIONAL SETTINGS MENU TREE REGIONAL SETTINGS CHANGE DATE CHANGE TIME ACK ACK SET MONTH ACK SET HOUR ACK SET DAY SET YEAR SET DAY OF WEEK ACK...

Страница 19: ...NEXT MENU ITEM ACK LOW PRESSURE ALARM ACK SET LOW PRESSURE ALARM ACK MENU HOURLY PRESSURE RECORDING ACK SET HOURLY PRESSURE RECORDING ACK MENU HIGH PRESSURE ALARM ACK SET HIGH PRESSURE ALARM ACK MENU...

Страница 20: ...IOD TIMER ACK SET RPT START MODE ACK SET DAY SET TIME SET TEST INTERVAL ACK ACK ACK ACK NEXT MENU ITEM NEXT MENU ITEM MENU MENU NEXT MENU ITEM SEQUENTIAL START TIMER ACK SET SEQUENTIAL START TIMER ACK...

Страница 21: ...roller Effective June 2011 EATON CORPORATION www ceaton com 21 APPENDIX E CUSTOM INPUT OUTPUT MENU TREE CUSTOM INPUT OUTPUT CUSTOM INPUTS CUSTOM OUTPUTS ACK ACK GO TO APPENDIX E a ACK GO TO APPENDIX E...

Страница 22: ...ER A C K M EN U C O M M O N ALAR M R ELAY A C K SET C O M M O N ALAR M R ELAY A C K M EN U LIN K TO R ELAY A C K SET LIN K TO R ELAY A C K N EXT M EN U ITEM M EN U LIN K TO LIG H T A C K SET LIN K TO...

Страница 23: ...MENU TREE CUSTOM OUTPUTS SELECT RELAY SELECT ALARM TYPE ACK MENU MENU NEXT MENU ITEM AUDIBLE ALARM ACK SET AUDIBLE ALARM ACK MENU FAIL SAFE ACK SET FAIL SAFE ACK MENU DELAY TIMER ACK SET DELAY TIMER N...

Страница 24: ...5805019K EATON Diesel Plus Effective June 2011 Diesel Engine Fire Pump Controller 24 EATON CORPORATION www eaton com APPENDIX E c CUSTOM LIGHTS MENU TREE CUSTOM LIGHTS SELECT LIGHT SELECT TYPE ACK MEN...

Страница 25: ...iesel Engine Fire Pump Controller Effective June 2011 EATON CORPORATION www ceaton com 25 APPENDIX F MAIN MENU PASSWORD MENU TREE MENU MAIN MENU PASSWORD SELECT PASSWORD ACK ACK SELECT BUTTON 1 SELECT...

Страница 26: ...Controller 26 EATON CORPORATION www eaton com APPENDIX G CUSTOM MESSAGE LOAD ACTIVATION DATA SELECT CUSTOM MESSAGES SELECT LOAD ACK ACK CUSTOM MESSAGES WILL BE UPLOADED DATA SELECT CUSTOM MESSAGES ACK...

Страница 27: ...ler Effective June 2011 EATON CORPORATION www ceaton com 27 APPENDIX K For control wiring use 14 AWG wire for all electrical connections except battery connections For battery connection terminals 6 7...

Страница 28: ...Test Fail An Engine Test has been initiated however an engine start has not occurred Fail to Start An Engine start has been initiated however the controller has failed to receive an engine run signal...

Страница 29: ...is 0 seconds automatic start will be delayed by the number of seconds programmed 9 2 Manual Start Test Turn the mode selector switch to the Manual position Press the Crank 1 pushbutton The Engine wil...

Страница 30: ...ekly Exerciser preprogram the controller to initiate the test at a time suitable to the user Turn the mode selector switch to the AUTO position At the programmed time and date the drain valve solenoid...

Страница 31: ...ser of this equipment is the contract between the purchaser and EATON NO WARRANTIES EXPRESSED OR IMPLIED INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY OR WARRANTIES ARISI...

Страница 32: ...rporation All Rights Reserved Printed in Canada Publication No IM05805019K June 2011 Eaton Corporation 10725 25th Street NE 124 Calgary Alberta Canada T3N 0A4 Phone 1 403 717 2000 Fax 1 403 717 0567 e...

Отзывы: