O & M Manual IM05805019K

EATON Diesel Plus

Effective June 2011

Diesel Engine Fire Pump Controller

28

EATON CORPORATION

 www.eaton.com

APPENDIX L: ALARM/STATUS MESSAGES 

Message

Description

AC Fail

Controller has detected AC Power Failure

AC Failure Start

The controller has started due to the loss of AC power.  Starting delay is an adjustable menu item.

Auto Crank #1

The controller has initiated an automatic crank on starter #1

Auto Crank #2

The controller has initiated an automatic crank on starter #2

Auto Mode

The controller is in Automatic mode

Battery #1 Failure

The controller is receiving a signal that detects a weak or discharged battery

Battery #2 Failure

The controller is receiving a signal that detects a weak or discharged battery

Charger #1 Fail

The AC supply power to Charger #1 is lost or has malfunctioned.

Charger #2 Fail

The AC supply power to Charger #2 is lost or has malfunctioned.

Config. Data Changed

Changes have been made to the controller configuration.  Modified menu items will be listed with new value.

Coil #1 Failure

Starter Coil #1 in the engine has failed or has been disconnected.

Coil #2 Failure

Starter Coil #2 in the engine has failed or has been disconnected.

Manual Crank #1

The Crank #1 pushbutton has been pressed

Manual Crank #2

The Crank #2 pushbutton has been pressed

Deluge Valve Start

The controller started the engine after it received a deluge valve start signal

Deluge Valve Off

The input to the deluge valve terminals has been removed

ECM in Alt Position

This is a signal sent to the controller to state the engine has switched to the alternate ECM module

Engine Overspeed

The controller has shutdown the engine due to an overspeed condition.

Engine Running

An engine run signal has been received from the engine.

Engine Stopped

The engine run signal is no longer being received

Engine Test Start

The engine has started on an engine test

Engine Test Fail

An Engine Test has been initiated, however an engine start has not occurred.

Fail to Start

An Engine start has been initiated, however the controller has failed to receive an engine run signal before the completion of the 
crank cycle.

Fuel Injection Malfunction An alarm received by the engine signaling the controller that there is no fuel reaching the injectors
Fuel Stop

The Fuel Stop relay in the controller has been energized

High Engine Temperature

Indicates that the coolant temperature in the water jacket is extremely hot.

High Temp Shutdown

Controller has shutdown due to a High Engine Temperature. (Engine/Weekly test only)

High Pressure

The system pressure is above the programmed high pressure alarm set point

HR: Pres xxx PSI

Hourly Pressure recording value.  Enabled in the menu.

Interlock Off

The interlock signal has been removed

Interlock On

The interlock signal has been received

Interlock Shutdown

The pump has been shutdown due to an interlock signal

Low Foam Level

The controller has received a low foam level signal

Low Fuel

A signal has been received from a remote contact indicating a Low Fuel condition.

Low Oil Pressure

The engine is showing low oil pressure

Low Pressure

The system pressure has dropped below the programmed pressure start point

Low Suction

The controller has received a low suction signal

Low Suction Shutdown

The controller has shutdown because of low suction

Manual Crank #1

The Controller was started via the Manual Crank button.

Manual Crank #2

The Controller was started via the Manual Crank button.

Manual Mode

The controller is in Manual mode.

Manual Stop Request

The Stop pushbutton on the controller has been pressed

Menu Entered

The menu system was entered by a user

Off Mode

The controller is in Off mode

Pressure xxx PSI

System pressure readings the controller has recorded. Frequency adjusted via Pressure Deviation in the menu.

Pump Start

The pump has started via a pump start signal

Pump Start Off

The input to the Pump Start terminals has been removed

Remote Start

The pump has started via a remote start signal

Содержание Diesel Plus 4A55737H01

Страница 1: ...Powering Business Worldwide EATON Diesel Plus Diesel Engine Fire Pump Controller O M Manual IM05805019K Effective June 2011...

Страница 2: ...2 Control Input Descriptions 9 4 3 3 Loss of DC Power 9 4 3 4 Speed Switch Malfunction 9 4 3 5 Engine Starter Coil Failure 9 4 3 6 Audible Alarm Silencing 9 4 3 7 Power Failure Alarm 10 4 4 Output Re...

Страница 3: ...utual FM Canadian Standards Association CSA New York Department of Buildings NYSB and meet CE and U B C C B C Seismic approval requirements 2 INSTALLATION AND EL ECTRICAL CONNECTIONS 2 1 Mounting Care...

Страница 4: ...y electronic and will protect itself by shutting down during a short circuit condition The maximum current draw that the chargers will draw when operating at 100 charging rate is 12 Volt System 24 Vol...

Страница 5: ...ttery charger cycle with NiCad batteries set DIP switches 3 and 6 to the ON position and all other DIP switches to the OFF position 3 1 7 Forced Charging There is provision for the battery chargers to...

Страница 6: ...ng a start signal from special starting equipment This is a normally closed contact that is required to be opened to start A factory installed jumper wire must be removed to use these contacts Termina...

Страница 7: ...ter button will allow the user to enter exit the message history statistics and diagnostics When in the menu system the enter button will allow the user to change the programmed set points and navigat...

Страница 8: ...g the cranking sequence Once the engine is running the controller will stop all further cranking STOP Modes The Stop Mode is programmable for Auto Shutdown On or Off see Appendix C Note that the engin...

Страница 9: ...er is factory installed The jumper must be removed in order to utilize this optional input Pump Start Terminal 36 When this input is in the Connected state the Diesel Plus controller will initiate an...

Страница 10: ...er Fail To Start After 6 cranking attempts three attempts per battery the Fail To Start annunciator will illuminate Attention to the diesel and its associated equipment is required immediately High En...

Страница 11: ...l initiate a start sequence Pressure Stop Point The value programmed determines the pressure the system must reach before the controller will automatically stop the fire pump motor via the running per...

Страница 12: ...sed on either of two separate conditions the stop pressure point or when the engine has started to run If the RPT is programmed to start at the Stop Pressure the timer will start timing once the syste...

Страница 13: ...en Timer A timer can be programmed to delay the time before the alarm becomes active Default value is 0 seconds Range is 0 500 seconds The timer will reset if the input is removed before the time has...

Страница 14: ...r to Appendix L for common messages and their meaning Refer to Section 7 to save the message history to a USB storage device or to view the message history on the optional embedded webpage 6 2 Statist...

Страница 15: ...r on press the Data Print button The first selection is Save to USB Press the Ack Alarm button and the controller will save the information to the USB storage device There will be five 5 files saved t...

Страница 16: ...t is as follows MMDDYYHHMM Month Day Year Hour Minute If any value entered between 1 and 9 needs to be lead by a 0 For example January 1 2009 8 15AM needs to be entered as 0101090815 NOTE All cells ne...

Страница 17: ...aton com 17 APPENDIX A MAIN MENU TREE MENU PASSWORD LANGUAGE REGIONAL SETTINGS PRESSURE SETTINGS TIMER VALUES CUSTOM INPUT OUTPUT SYSTEM CONFIG MENU MAIN MENU PASSWORD ACK ACK SELECT LANGUAGE ACK GO T...

Страница 18: ...p Controller 18 EATON CORPORATION www eaton com APPENDIX B REGIONAL SETTINGS MENU TREE REGIONAL SETTINGS CHANGE DATE CHANGE TIME ACK ACK SET MONTH ACK SET HOUR ACK SET DAY SET YEAR SET DAY OF WEEK ACK...

Страница 19: ...NEXT MENU ITEM ACK LOW PRESSURE ALARM ACK SET LOW PRESSURE ALARM ACK MENU HOURLY PRESSURE RECORDING ACK SET HOURLY PRESSURE RECORDING ACK MENU HIGH PRESSURE ALARM ACK SET HIGH PRESSURE ALARM ACK MENU...

Страница 20: ...IOD TIMER ACK SET RPT START MODE ACK SET DAY SET TIME SET TEST INTERVAL ACK ACK ACK ACK NEXT MENU ITEM NEXT MENU ITEM MENU MENU NEXT MENU ITEM SEQUENTIAL START TIMER ACK SET SEQUENTIAL START TIMER ACK...

Страница 21: ...roller Effective June 2011 EATON CORPORATION www ceaton com 21 APPENDIX E CUSTOM INPUT OUTPUT MENU TREE CUSTOM INPUT OUTPUT CUSTOM INPUTS CUSTOM OUTPUTS ACK ACK GO TO APPENDIX E a ACK GO TO APPENDIX E...

Страница 22: ...ER A C K M EN U C O M M O N ALAR M R ELAY A C K SET C O M M O N ALAR M R ELAY A C K M EN U LIN K TO R ELAY A C K SET LIN K TO R ELAY A C K N EXT M EN U ITEM M EN U LIN K TO LIG H T A C K SET LIN K TO...

Страница 23: ...MENU TREE CUSTOM OUTPUTS SELECT RELAY SELECT ALARM TYPE ACK MENU MENU NEXT MENU ITEM AUDIBLE ALARM ACK SET AUDIBLE ALARM ACK MENU FAIL SAFE ACK SET FAIL SAFE ACK MENU DELAY TIMER ACK SET DELAY TIMER N...

Страница 24: ...5805019K EATON Diesel Plus Effective June 2011 Diesel Engine Fire Pump Controller 24 EATON CORPORATION www eaton com APPENDIX E c CUSTOM LIGHTS MENU TREE CUSTOM LIGHTS SELECT LIGHT SELECT TYPE ACK MEN...

Страница 25: ...iesel Engine Fire Pump Controller Effective June 2011 EATON CORPORATION www ceaton com 25 APPENDIX F MAIN MENU PASSWORD MENU TREE MENU MAIN MENU PASSWORD SELECT PASSWORD ACK ACK SELECT BUTTON 1 SELECT...

Страница 26: ...Controller 26 EATON CORPORATION www eaton com APPENDIX G CUSTOM MESSAGE LOAD ACTIVATION DATA SELECT CUSTOM MESSAGES SELECT LOAD ACK ACK CUSTOM MESSAGES WILL BE UPLOADED DATA SELECT CUSTOM MESSAGES ACK...

Страница 27: ...ler Effective June 2011 EATON CORPORATION www ceaton com 27 APPENDIX K For control wiring use 14 AWG wire for all electrical connections except battery connections For battery connection terminals 6 7...

Страница 28: ...Test Fail An Engine Test has been initiated however an engine start has not occurred Fail to Start An Engine start has been initiated however the controller has failed to receive an engine run signal...

Страница 29: ...is 0 seconds automatic start will be delayed by the number of seconds programmed 9 2 Manual Start Test Turn the mode selector switch to the Manual position Press the Crank 1 pushbutton The Engine wil...

Страница 30: ...ekly Exerciser preprogram the controller to initiate the test at a time suitable to the user Turn the mode selector switch to the AUTO position At the programmed time and date the drain valve solenoid...

Страница 31: ...ser of this equipment is the contract between the purchaser and EATON NO WARRANTIES EXPRESSED OR IMPLIED INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY OR WARRANTIES ARISI...

Страница 32: ...rporation All Rights Reserved Printed in Canada Publication No IM05805019K June 2011 Eaton Corporation 10725 25th Street NE 124 Calgary Alberta Canada T3N 0A4 Phone 1 403 717 2000 Fax 1 403 717 0567 e...

Отзывы: