O & M Manual IM05805019K

EATON Diesel Plus

Effective June 2011

Diesel Engine Fire Pump Controller

8

EATON CORPORATION

 www.eaton.com

4.2 Start Sequence

In the Automatic Mode the Diesel Plus controller will 
automatically start and stop the fire pump motor as dictated by 
the features supplied and their programmed set-point values. A 
summary of the controller intelligence and supervisory circuits 
that constantly monitor the condition of the system pressure, 
inputs, and system alarm points is provided.

4.2.1 Manual Start Sequence

Manual start is defined as a remote start. Whenever the engine 
is running via a manual start, the motor needs to be manually 
stopped via the stop pushbutton located on the enclosure 
flange or by placing the controller in off mode.

4.2.2 Automatic Start Sequence

Automatic start is defined as a low-pressure pump start contact 
closure, and Deluge Valve start condition. (Terminals 11 and 36) 
Whenever the engine is running via an automatic start the 
engine can be automatically stopped. In order for the controller 
to automatically stop the engine automatic stopping must be 
enabled, the RPT must be finished its timing cycle and no 
starting conditions can exist. If the controller is programmed 
for automatic shutdown, the motor needs to be manually 
stopped via the local stop pushbutton located on the enclosure 
flange or by placing the controller in the off mode.

OFF Mode

In the OFF position the controller will not attempt to start the 
engine for any reason. Off mode also resets and silences all 
alarms.

MANUAL Mode

This position allows the starting of the engines using the 
manual crank buttons, Crank #1 and Crank #2, are located on 
the enclosure flange. For added cranking capacity, both Crank 
buttons can be depressed simultaneously.

The engine can be stopped by the “Local Stop” pushbutton or 
by placing the controller in the OFF mode. The engine will 
automatically stop in the case of an OVERSPEED condition.

All alarms, except for “FAIL TO START”, are active in the 
MANUAL mode.

CAUTION

Only depress Crank #1 or Crank #2 pushbuttons with controller in the 
“MANUAL” mode. 

Do not depress the crank pushbuttons in any other mode or while engine is 
running. Doing so can result in serious damage to the engine.

AUTO Mode

A drop in pressure, “Remote Start” signal, “Pump Start” signal, 
a signal from the “Deluge Valve” or Weekly Test Timer will 
initiate the “attempt to start” cycle. This cycle consists of 6 
crank periods of 15 seconds duration separated by 5 rest 
periods of 15 seconds duration. Battery 1 and Battery 2 are 
alternated for each crank cycle. In the event that one battery is 
inoperative or missing, the controller will lock-in on the 
remaining battery during the cranking sequence. Once the 
engine is running, the controller will stop all further cranking.

STOP Modes

The Stop Mode is programmable for Auto Shutdown - On or Off 
(see Appendix C). Note that the engine can be stopped in many 
cases by pressing the local stop push button or at any time by 
placing the controller in the OFF position or automatically in 
case of an OVERSPEED condition.

Manual Stop Mode:

 The engine will continue to run until the 

“Local Stop” pushbutton is depressed - providing all starting 
causes have been eliminated.

Auto Shutdown:

 The engine will continue to run until the 

running period timer (RPT) has timed out and all starting 
causes have been eliminated. 

Weekly Test Timer

Each Diesel Plus controller is equipped with a Weekly Test 
Timer, to automatically exercise the engine in one week 
intervals, based on the programmed setting. The controller 
initiates the starting sequence by opening a drain valve 
resulting in a simulated system pressure loss. The drain valve 
is automatically closed once the controller receives a Low 
Pressure signal. The engine will continue to run for the 
programmed duration. “Weekly Test Started” will be saved into 
the controller memory.

In order to protect the engine, during the Weekly Test sequence, 
an OVERSPEED condition, LOW OIL PRESSURE or HIGH 
ENGINE TEMP alarm will automatically shutdown the engine.

Engine Test Pushbutton

Pressing the Engine Test pushbutton initiates a starting 
sequence by opening the drain valve resulting in a pressure 
loss. The controller will start the engine in the automatic mode.

The TEST sequence can be terminated by putting the controller 
in the OFF mode, otherwise the STOP mode prevails as 
programmed.

All alarms are active in the test mode. In order to protect the 
engine, in the test mode, an OVERSPEED condition, LOW OIL 
PRESSURE or HIGH ENGINE TEMP alarm will automatically 
shutdown the engine. 

4.2.3 Run Period Timer

The RPT is only active when active when the auto stop is set

to "On". The Run Period Timer (RPT) performs the automatic 
stopping function in the controller. After a start initiated by the 
pressure sensor or via the “Pump Start” input the controller will 
start and run for the duration of the RPT.

The purpose of the RPT is to ensure that the engine is not 
subjected to frequent starts in response to the pressure. Refer 
to Appendix D for programming of the RPT. 

4.2.4 Sequential Start Timer

The Sequential Start Timer is standard in all Diesel Plus fire 
pump controllers.

The controller for each unit of multiple pump units shall 
incorporate a sequential timing device to prevent any one 
driver from starting  simultaneously with any other driver. 

Each pump supplying suction pressure to another pump shall 
be arranged to start within 10 seconds before the pump it 
supplies. The controllers for pumps arranged in series shall

 be interlocked to ensure the correct pump starting sequence. 

Содержание Diesel Plus 4A55737H01

Страница 1: ...Powering Business Worldwide EATON Diesel Plus Diesel Engine Fire Pump Controller O M Manual IM05805019K Effective June 2011...

Страница 2: ...2 Control Input Descriptions 9 4 3 3 Loss of DC Power 9 4 3 4 Speed Switch Malfunction 9 4 3 5 Engine Starter Coil Failure 9 4 3 6 Audible Alarm Silencing 9 4 3 7 Power Failure Alarm 10 4 4 Output Re...

Страница 3: ...utual FM Canadian Standards Association CSA New York Department of Buildings NYSB and meet CE and U B C C B C Seismic approval requirements 2 INSTALLATION AND EL ECTRICAL CONNECTIONS 2 1 Mounting Care...

Страница 4: ...y electronic and will protect itself by shutting down during a short circuit condition The maximum current draw that the chargers will draw when operating at 100 charging rate is 12 Volt System 24 Vol...

Страница 5: ...ttery charger cycle with NiCad batteries set DIP switches 3 and 6 to the ON position and all other DIP switches to the OFF position 3 1 7 Forced Charging There is provision for the battery chargers to...

Страница 6: ...ng a start signal from special starting equipment This is a normally closed contact that is required to be opened to start A factory installed jumper wire must be removed to use these contacts Termina...

Страница 7: ...ter button will allow the user to enter exit the message history statistics and diagnostics When in the menu system the enter button will allow the user to change the programmed set points and navigat...

Страница 8: ...g the cranking sequence Once the engine is running the controller will stop all further cranking STOP Modes The Stop Mode is programmable for Auto Shutdown On or Off see Appendix C Note that the engin...

Страница 9: ...er is factory installed The jumper must be removed in order to utilize this optional input Pump Start Terminal 36 When this input is in the Connected state the Diesel Plus controller will initiate an...

Страница 10: ...er Fail To Start After 6 cranking attempts three attempts per battery the Fail To Start annunciator will illuminate Attention to the diesel and its associated equipment is required immediately High En...

Страница 11: ...l initiate a start sequence Pressure Stop Point The value programmed determines the pressure the system must reach before the controller will automatically stop the fire pump motor via the running per...

Страница 12: ...sed on either of two separate conditions the stop pressure point or when the engine has started to run If the RPT is programmed to start at the Stop Pressure the timer will start timing once the syste...

Страница 13: ...en Timer A timer can be programmed to delay the time before the alarm becomes active Default value is 0 seconds Range is 0 500 seconds The timer will reset if the input is removed before the time has...

Страница 14: ...r to Appendix L for common messages and their meaning Refer to Section 7 to save the message history to a USB storage device or to view the message history on the optional embedded webpage 6 2 Statist...

Страница 15: ...r on press the Data Print button The first selection is Save to USB Press the Ack Alarm button and the controller will save the information to the USB storage device There will be five 5 files saved t...

Страница 16: ...t is as follows MMDDYYHHMM Month Day Year Hour Minute If any value entered between 1 and 9 needs to be lead by a 0 For example January 1 2009 8 15AM needs to be entered as 0101090815 NOTE All cells ne...

Страница 17: ...aton com 17 APPENDIX A MAIN MENU TREE MENU PASSWORD LANGUAGE REGIONAL SETTINGS PRESSURE SETTINGS TIMER VALUES CUSTOM INPUT OUTPUT SYSTEM CONFIG MENU MAIN MENU PASSWORD ACK ACK SELECT LANGUAGE ACK GO T...

Страница 18: ...p Controller 18 EATON CORPORATION www eaton com APPENDIX B REGIONAL SETTINGS MENU TREE REGIONAL SETTINGS CHANGE DATE CHANGE TIME ACK ACK SET MONTH ACK SET HOUR ACK SET DAY SET YEAR SET DAY OF WEEK ACK...

Страница 19: ...NEXT MENU ITEM ACK LOW PRESSURE ALARM ACK SET LOW PRESSURE ALARM ACK MENU HOURLY PRESSURE RECORDING ACK SET HOURLY PRESSURE RECORDING ACK MENU HIGH PRESSURE ALARM ACK SET HIGH PRESSURE ALARM ACK MENU...

Страница 20: ...IOD TIMER ACK SET RPT START MODE ACK SET DAY SET TIME SET TEST INTERVAL ACK ACK ACK ACK NEXT MENU ITEM NEXT MENU ITEM MENU MENU NEXT MENU ITEM SEQUENTIAL START TIMER ACK SET SEQUENTIAL START TIMER ACK...

Страница 21: ...roller Effective June 2011 EATON CORPORATION www ceaton com 21 APPENDIX E CUSTOM INPUT OUTPUT MENU TREE CUSTOM INPUT OUTPUT CUSTOM INPUTS CUSTOM OUTPUTS ACK ACK GO TO APPENDIX E a ACK GO TO APPENDIX E...

Страница 22: ...ER A C K M EN U C O M M O N ALAR M R ELAY A C K SET C O M M O N ALAR M R ELAY A C K M EN U LIN K TO R ELAY A C K SET LIN K TO R ELAY A C K N EXT M EN U ITEM M EN U LIN K TO LIG H T A C K SET LIN K TO...

Страница 23: ...MENU TREE CUSTOM OUTPUTS SELECT RELAY SELECT ALARM TYPE ACK MENU MENU NEXT MENU ITEM AUDIBLE ALARM ACK SET AUDIBLE ALARM ACK MENU FAIL SAFE ACK SET FAIL SAFE ACK MENU DELAY TIMER ACK SET DELAY TIMER N...

Страница 24: ...5805019K EATON Diesel Plus Effective June 2011 Diesel Engine Fire Pump Controller 24 EATON CORPORATION www eaton com APPENDIX E c CUSTOM LIGHTS MENU TREE CUSTOM LIGHTS SELECT LIGHT SELECT TYPE ACK MEN...

Страница 25: ...iesel Engine Fire Pump Controller Effective June 2011 EATON CORPORATION www ceaton com 25 APPENDIX F MAIN MENU PASSWORD MENU TREE MENU MAIN MENU PASSWORD SELECT PASSWORD ACK ACK SELECT BUTTON 1 SELECT...

Страница 26: ...Controller 26 EATON CORPORATION www eaton com APPENDIX G CUSTOM MESSAGE LOAD ACTIVATION DATA SELECT CUSTOM MESSAGES SELECT LOAD ACK ACK CUSTOM MESSAGES WILL BE UPLOADED DATA SELECT CUSTOM MESSAGES ACK...

Страница 27: ...ler Effective June 2011 EATON CORPORATION www ceaton com 27 APPENDIX K For control wiring use 14 AWG wire for all electrical connections except battery connections For battery connection terminals 6 7...

Страница 28: ...Test Fail An Engine Test has been initiated however an engine start has not occurred Fail to Start An Engine start has been initiated however the controller has failed to receive an engine run signal...

Страница 29: ...is 0 seconds automatic start will be delayed by the number of seconds programmed 9 2 Manual Start Test Turn the mode selector switch to the Manual position Press the Crank 1 pushbutton The Engine wil...

Страница 30: ...ekly Exerciser preprogram the controller to initiate the test at a time suitable to the user Turn the mode selector switch to the AUTO position At the programmed time and date the drain valve solenoid...

Страница 31: ...ser of this equipment is the contract between the purchaser and EATON NO WARRANTIES EXPRESSED OR IMPLIED INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY OR WARRANTIES ARISI...

Страница 32: ...rporation All Rights Reserved Printed in Canada Publication No IM05805019K June 2011 Eaton Corporation 10725 25th Street NE 124 Calgary Alberta Canada T3N 0A4 Phone 1 403 717 2000 Fax 1 403 717 0567 e...

Отзывы: