Configuration Using the PROFIBUS Configuration File
22
C441 PROFIBUS Module User Manual
MN042002EN—July 2015
www.eaton.com
Motor Control Input Configuration
S811 input#1 cfg 2 bytes
S811 input#2 cfg 2 bytes
S811 input#3 cfg 2 bytes
S811 input#4 cfg 2 bytes
Network input#1 cfg 2 bytes
Network input#2 cfg 2 bytes
Network input#3 cfg 2 bytes
Network input#4 cfg 2 bytes
S811+
0 = No function
1 = Run1
2 = Ramp2
3 = Jog
4 = Local control enable
5 = Fault reset
6 = E-stop input
7 = Alarm-No-Trip
8 = External Trip
9 = External Warning
10 = Disable overload on start
11 = Analog Input (S811 input #4 only)
Analog Input Data Range
S811+
Value
Description
0x01 not supported
0x02 0–20 mA range
0x03 4–20 mA range
Motor Control Output Configuration
S811 output#1 cfg 2 bytes
S811 output#2 cfg 2 bytes
Network output#1 cfg 2 bytes
Network output#2 cfg 2 bytes
S811+
0 = No function
1 = Faulted
2 = Not Faulted
3 = Bypass
4 = Not Bypass
5 = Motor Energized
6 = Motor Not Energized
7 = Warning
8 = Not Warning
9 = Custom Codes
10 = Not Custom Codes
Fault Reset Mode
S811+
0 = Manual reset
1 = Auto reset
2 = Power on reset
Auto Reset Delay Time
S811+
0.1–600.0 sec (in 0.1 sec)
Auto Reset Number of Reset Attempts Limit
S811+
0–10000
Overload Fault Enable
S811+
0 = Protection disabled
1 = Fault enabled
2 = Warning enabled
Motor Overload During Start Enable
S811+
1 = enable
0 = disable
Phase Reversal Fault Enable
S811+
0 = Protection disabled
1 = Fault enabled
2 = Warning enabled
Motor Undercurrent Fault (Warning) Trip Enable
S811+
0 = Protection disabled
1 = Fault enabled
2 = Warning enabled
Motor Undercurrent Fault Trip Level (% FLA)
S811+
0–100%
Motor Undercurrent Fault Duration
S811+
0.1–60.0 sec (in 0.1 sec)
Motor Jam Fault Enable
S811+
0 = Protection disabled
1 = Fault enabled
2 = Warning enabled
Motor Stall Fault Enable
S811+
0 = Protection disabled
1 = Fault enabled
2 = Warning enabled
Motor Phase Loss Fault Enable
S811+
0 = Protection disabled
1 = Fault enabled
2 = Warning enabled
Table 20. S811+ Soft Starter Configuration File, continued
Parameter Name
Location
Notes