Configuration Using the PROFIBUS Configuration File
C441 PROFIBUS Module User Manual
MN042002EN—July 2015
www.eaton.com
19
S611 Soft Starter
Table 19. S611 Soft Starter Configuration File
Parameter Name
Location
Notes
Extended User Parameter Data
Enable Device Parameterization
Adapter
0 = Ignore user data, 1 = Download Device Parameters
Com Adapter Outputs ComLoss Behavior
Adapter
0 = Fail Safe (outputs disabled), 1 = Hold Last state
Overload FLA
S611
Motor full load amp rating (in 0.1A)
Overload Trip Class
S611
Trip class 5, 10, 20, & 30
Start Method
S611
Voltage ramp start
Current limit start
Pump start
Start Time
S611
Length of start in 0.1 sec. (5–1800)
Initial Torque
S611
Initial starting torque applied to motor at beginning of the start profile. (0–100%)
Stop Time*
S611
Length of stop ramp in 0.1 sec. (0–600)
0 sec = disabled
Pump Stop Time*
S611
Length of pump stop ramp in 0.1sec. (50–1200)
Kick Start Time
S611
Length of time to apply kick torque in 0.1 sec. (0–20)
Setting time to 0sec disables kick torque setting.
Kick Start Torque
S611
Kick torque applied to motor at beginning of the start profile. (0–100%). Only
Motor Rated Voltage
S611
Nameplate Rated motor voltage. (115–600 V)
Under Voltage Percent
S611
Under voltage fault threshold. (% rated motor voltage) (1–99%)
Under Voltage Trip Delay
S611
Length of under voltage condition before fault in sec. (0–20)
Over Voltage Percent
S611
Over voltage fault threshold. (% rated motor voltage) (101–120%)
Over Voltage Trip Delay
S611
Length of over voltage condition before fault in sec. (0–20)
Voltage Imbalance Percent
S611
Voltage Imbalance fault threshold. (% rated motor voltage) (1–20%)
Voltage Imbalance Trip Delay
S611
Length of voltage imbalance condition before fault in sec. (0–20)
Phase Sequence
S611
Incoming voltage phase sequence
ABC
ACB
Reset Mode
S611
Fault Reset mode
Manual Reset
Auto Reset
Enable Overload trip
S611
0 = disable fault
1 = enable fault
Enable Jam trip
S611
0 = disable fault
1 = enable fault
Enable Stall trip
S611
0 = disable fault
1 = enable fault
Enable Current Imbalance
S611
0 = disable fault
1 = enable fault
Enable Load Disconnect trip
S611
0 = disable fault
1 = enable fault
Enable Phase Loss trip
S611
0 = disable fault
1 = enable fault
Enable Under Voltage trip
S611
0 = disable fault
1 = enable fault
Enable Over Voltage trip
S611
0 = disable fault
1 = enable fault
Enable Voltage Imbalance trip
S611
0 = disable fault
1 = enable fault