PROFIBUS I/O Parameters
C441 PROFIBUS Module User Manual
MN042002EN—July 2015
www.eaton.com
25
PROFIBUS I/O Parameters
Cyclic IO Data for C441, C440, S611, S811+ and
Stand-Alone I/O
There is a different Base Module that must be entered into
the Base Module Slot in a PROFIBUS master’s software for
each of the devices the C441 PROFIBUS modules interface
to the PROFIBUS network. The Base modules are defined in
the GSD file for the C441Q/S/QS/SS. The default Base
module is the “IO StandAlone Base”. The other Base
Modules are as follows:
●
C441 Motor Insight Base
●
C440 Overload Base
●
S611 Soft Starter Base
●
S811 Soft Starter Base
By default, the first 2 Data Exchange Module slots, from the
GSD file contain the following:
●
Com Adapter Outputs_1
●
Control for the 2 outputs on the C441Q/S/QS/SS module
●
Com Adapter Inputs_1
●
Status of the 4 inputs on the C441Q/S/QS/SS module
These first 2 modules are used with all Base Modules.
A third parameter may also be used with all of the Base
modules: “Com Adapter Status”. Following the first
2 parameters are the optional data shown below for each
supported device, based on the Base Module used. If the
IO StandAlone Base is used, only the COM Adapter
Outputs_1, Com Adapter Inputs_1 and Com Adapter
Status Data Exchange Parameters may be used.