Configuration Using the PROFIBUS Configuration File
C441 PROFIBUS Module User Manual
MN042002EN—July 2015
www.eaton.com
15
Configuration Using the PROFIBUS Configuration File
The C441 PROFIBUS adapters give the user the ability to
enable/disable protections, set up trip thresholds, set up trip
delays, and reset delays for the C441 Motor Insight relay, the
C440 Overload relay, the S611 Soft Starter and the S811+
Soft Starter over a PROFIBUS network.
Upon reception of the parameterization telegram, device
parameter data is range checked. If the data is outside the
range specified in the GSD file, the parameterization will be
rejected and parameterization will fail. Data for parameters
such as Overload FLA, Low kW Trip Level, High kW Trip
Level, and GND Fault Trip Level whose ranges vary based on
model will be “adjusted.” If the value is greater than the
maximum allowed value, the parameter is set to its
maximum value. Likewise, if a parameter is set to a value
less than its minimum value, the parameter will be set to its
minimum value.
Note:
Values must still fall within the range specified in the
GSD file for parameterization to be successful.
Notice
The “Enable Device Parameterization” parameter must be
enabled for the connected device parameters to be
downloaded into the device. If the “Enable Device
Parameterization” parameter is set to “Ignore” (0), device
parameters are “ignored” by the C441 PROFIBUS adapter
and are not downloaded into the connected device.