20
Eaton BladeUPS 5 kVA to 60 kVA (N+1) User’s Guide 164201649—Rev 14
•
NOTE
You may find it useful to use a magnetized screwdriver when removing or replacing
mounting screws.
33..44
FFlloooorr LLooaaddiinngg
When planning the installation, consider the system weight for floor loading. The strength of the installation
surface must be adequate for point and distributed loadings. Approximate weights are shown in
Table 1. Weights
Number of UPSs
Shipping Weight (Pallet, Rack, Wireway,
BladeUPS Bar, and UPSs)
System Weight (Excludes Pallet)
1
471.7 kg (1040 lb)
304.8 kg (672 lb)
2
617.8 kg (1362 lb)
450.9 kg (994 lb)
3
763.9 kg (1684 lb)
596.9 kg (1316 lb)
4
909.9 kg (2006 lb)
743.0 kg (1638 lb)
5
1060.5 kg (2328 lb)
889.0 kg (1960 lb)
6
1202.0 kg (2650 lb)
1035.1 kg (2282 lb)
NOTE
When adding an MBM to the cabinet, cabinet weight will increase by 34.5 kg (76 lb).
33..55
M
Moovviinngg tthhee S
Syysstteem
m aanndd B
Baatttteerryy P
Paalllleettss
The system is bolted to a wooden pallet supported by wood skids. The batteries are stacked on a separate
pallet and are held in place with strap binding.
To move the system:
1.
Verify that the forklift or pallet jack is rated to handle the weight of the system ( see
for system
weight).
2.
If not already moved, use a forklift or pallet jack to move the system to the installation area, or as close as
possible. Insert the forklift jacks between the skids at the front of the pallet.
WARNING
The forklift jacks must be inserted between the skids at the front of the pallet (see
). If unloading
instructions are not closely followed, moving the system may cause serious injury.
Содержание BladeUPS none
Страница 8: ...viii Eaton BladeUPS 5 kVA to 60 kVA N 1 User s Guide 164201649 Rev 14 Table of Contents ...
Страница 12: ...xii Eaton BladeUPS 5 kVA to 60 kVA N 1 User s Guide 164201649 Rev 14 List of Figures ...
Страница 14: ...xiv Eaton BladeUPS 5 kVA to 60 kVA N 1 User s Guide 164201649 Rev 14 List of Tables ...
Страница 20: ...6 Eaton BladeUPS 5 kVA to 60 kVA N 1 User s Guide 164201649 Rev 14 Introduction ...
Страница 134: ...120 Eaton BladeUPS 5 kVA to 60 kVA N 1 User s Guide 164201649 Rev 14 Metering ...
Страница 160: ...16420164914 164201649 14 ...