Eaton BladeUPS 5 kVA to 60 kVA (N+1) User’s Guide 164201649—Rev 14
81
Figure 66. Installing the Blue Terminating Plug (Last UPS)
Blue Terminating Plug (CAN OUT)
11. Verify that only the first and last UPSs in the configuration have a blue terminating plug installed.
12. Using the supplied connectors, install a CAN Bridge Card cable between each UPS as shown in
,
connecting the CAN OUT port on one UPS to the CAN IN port on the next UPS.
On startup, the parallel system will identify the UPS wired after UNIT 1 as UNIT 2, and so forth.
NOTE
You can configure the parallel system with UPS 1 at the bottom of the rack (as shown in
or at the top of the rack.