Eaton BladeUPS 5 kVA to 60 kVA (N+1) User’s Guide 164201649—Rev 14
125
Figure 86. Installing the UPS Single-string Battery Trays for BladeUPS 5.0 kVA
7.
Reinstall the battery cover plate.
8.
Turn the battery circuit breaker to the ON (
) position (see
on page 75 ).
9.
Replace the UPS front cover (see
):
Plug the LCD cable from the control panel on the front cover into the connector on the electronics module.
Use care to loop the LCD cable gently in front of the electronics module.
Push the top of the front cover firmly into place, and then push the bottom firmly into place.
NOTE
Reconnecting the control panel to the electronics module automatically transfers the
UPS to Normal mode.
10. Verify that no alarms are indicated on the control panel.
Figure 87. Replacing the UPS Front Cover