Eaton BladeUPS 5 kVA to 60 kVA (N+1) User’s Guide 164201649—Rev 14
123
77..77
H
Hoow
w ttoo R
Reeppllaaccee U
UP
PS
S IInntteerrnnaall B
Baatttteerriieess
CAUTION
•
The UPS internal batteries are heavy (see page 140 ). Each battery tray holds two rows of five batteries.
Use caution when handling the heavy battery trays.
•
Pull the battery trays out onto a flat, stable surface. The battery trays are unsupported when you pull them
out of the UPS.
To replace the battery trays in the UPS cabinet:
1.
Verify that the battery circuit breaker is in the OFF (O) position (
).
2.
Remove the UPS front cover and set it aside (see
):
Figure 83. Removing the UPS Front Cover
LCD Cable
NOTE
Disconnecting the control panel from the electronics module automatically transfers the
UPS to Bypass mode.
3.
Remove the eight screws on the battery cover plate and retain. Remove the plate. See
.