74
Eaton BladeUPS 5 kVA to 60 kVA (N+1) User’s Guide 164201649—Rev 14
–
20A (BladeUPS 5.0 model)
•
Three-phase, 4-wire plus ground, 208Y/120V nominal (BladeUPS 12 model) with 5-pin IEC309-60 amp
receptacle or in-line connector (GH560C9W or similar).
•
Three-phase, 4-wire plus ground, 400Y/230V nominal, (380–415 Vac acceptable), (BladeUPS 12i model)
with 5-pin IEC309-30 amp receptacle or in-line connector, (GH532C6W or similar)
•
50/60 Hz
•
Wall-mounted breaker that is readily accessible to the operator
The BladeUPS models require the following input plug and receptacle :
Table 8. Required Plugs and Receptacles
BladeUPS Model
Input Plug
Receptacle
12i kVA
IEC309-32 (GH532P6W or similar)
GH532C6W (or similar)
12 kVA
IEC309-60 (GH560P9W or similar)
GH560C9W (or similar)
8 kVA
NEMA L21-30P
NEMA L21-30R
5.0 kVA
NEMA L21-20P
NEMA L21-20R
To install the UPS:
1.
Switch off utility power to the distribution point where the UPS will be connected. Be absolutely sure there
is no power.
2.
Verify that all circuit breakers are in the OFF (O) position.
NOTE
The load connector breaker controls the load connector only, not the output power cord.
3.
If you are installing power management software, connect your computer to the UPS communication port
or optional X-Slot card. For the communication port, use the supplied serial cable.
4.
If your rack has conductors for grounding or bonding of ungrounded metal parts, connect the ground cable
(not included) to the ground bonding screw.
5.
If an emergency power-off (disconnect) switch is required by local codes, install the REPO switch before
powering on the UPS.
6.
Plug in UPS plug into provided utility input receptacle or connector
7.
Plug power distribution (RPM or ePDU), into BladeUPS output connector or load connector.
8.
Continue to Standalone UPS Initial Startup.
Содержание BladeUPS none
Страница 8: ...viii Eaton BladeUPS 5 kVA to 60 kVA N 1 User s Guide 164201649 Rev 14 Table of Contents ...
Страница 12: ...xii Eaton BladeUPS 5 kVA to 60 kVA N 1 User s Guide 164201649 Rev 14 List of Figures ...
Страница 14: ...xiv Eaton BladeUPS 5 kVA to 60 kVA N 1 User s Guide 164201649 Rev 14 List of Tables ...
Страница 20: ...6 Eaton BladeUPS 5 kVA to 60 kVA N 1 User s Guide 164201649 Rev 14 Introduction ...
Страница 134: ...120 Eaton BladeUPS 5 kVA to 60 kVA N 1 User s Guide 164201649 Rev 14 Metering ...
Страница 160: ...16420164914 164201649 14 ...