Eaton BladeUPS 5 kVA to 60 kVA (N+1) User’s Guide 164201649—Rev 14
129
•
To remove the UPS front cover, grasp the finger grips on both sides of the cover and pull the cover
forward firmly. Unplug the LCD cable connecting the back of the control panel to the electronics
module.
•
To remove the electronics module, remove the electronics module locking screw at the top left of the
electronics module and retain. Grasp the ring handle at the middle of the module and pull the module
slowly out of the cabinet. Pull firmly to unseat the connectors. Use two hands to support the module.
NOTE
Treat the electronics module with care to avoid damaging the fans, connectors, or
internal circuitry.
10. Remove the eight screws on the battery cover plate and retain. Remove the plate. See a similar removal in
CAUTION
•
The UPS internal batteries are heavy. Each battery tray holds two rows of five batteries. Use caution when
handling the heavy battery trays.
•
Pull the battery trays out onto a flat, stable surface. The battery trays are unsupported when you pull them
out of the UPS.
11. Untuck the plastic handle at the end of a battery tray. Pull the handle firmly to remove the tray. Use both
hands to support the tray as it leaves the UPS cabinet.
Repeat for each battery tray. See the following section
Recycling the Used Battery or UPS
for proper
disposal.
12. Remove the CAN Bridge Card and any optional X-Slot card from its X-Slot communication bay.
13. Remove the UPS from the rack carefully to avoid damage to other equipment or the parallel input cord.
14. If not returning the UPS for warranty, see the following section ”Recycling the Used Battery or UPS” for
proper disposal.
15. If replacing UPS or placing UPS into service in a different parallel configuration, continue to section
“UPS Installation into an Existing Parallel System” .
77..1111
R
Reeccyycclliinngg tthhee U
Usseedd B
Baatttteerryy oorr U
UP
PS
S
Contact your local recycling or hazardous waste center for information on proper disposal of the used battery or
UPS.
WARNING
•
Do not dispose of the battery or batteries in a fire. Batteries may explode. Proper disposal of batteries is
required. Refer to your local codes for disposal requirements.
•
Do not open or mutilate the battery or batteries. Released electrolyte is harmful to the skin and eyes. It
may be toxic.
CAUTION
Do not discard the UPS or the UPS batteries in the trash. This product contains sealed, lead acid batteries and
must be disposed of properly. For more information, contact your local recycling/reuse or hazardous waste
center.
Содержание BladeUPS none
Страница 8: ...viii Eaton BladeUPS 5 kVA to 60 kVA N 1 User s Guide 164201649 Rev 14 Table of Contents ...
Страница 12: ...xii Eaton BladeUPS 5 kVA to 60 kVA N 1 User s Guide 164201649 Rev 14 List of Figures ...
Страница 14: ...xiv Eaton BladeUPS 5 kVA to 60 kVA N 1 User s Guide 164201649 Rev 14 List of Tables ...
Страница 20: ...6 Eaton BladeUPS 5 kVA to 60 kVA N 1 User s Guide 164201649 Rev 14 Introduction ...
Страница 134: ...120 Eaton BladeUPS 5 kVA to 60 kVA N 1 User s Guide 164201649 Rev 14 Metering ...
Страница 160: ...16420164914 164201649 14 ...