7
GH5 Activeline Beacon Technical Manual
GH5 ACTIVELINE BEACON TECHNICAL MANUAL
TMF0075.A
www.eaton.com
Technical specifications
Storage and transport temperature
-20°C…+70°C
Enclosure
Polycarbonate
Cap
Polycarbonate
Cable gland
M20 x 1.5
Clamp capacity of terminals
2.5 mm
2
Operating position
any position
Weight
appr. 1.4 kg
Operating modes
Continuous light
one colour:
the colour is continuously on
more than one colour:
990 ms turn-on time per colour
Blink light
one colour:
220 ms turn-on time, 275 ms turn-off time
more than one colour:
blinks 2 times per colour
Flash light
one colour:
55 ms turn-on time, 440 ms turn-off time
more than one colour:
flashes 4 times per colour
Change of colour
always in the order green-yellow-red-blue-white
Version with AC Voltage
Operating voltage (Voltage between
colour terminals and terminal „N“)
230 VAC, 50…60 Hz
Current consumption at 230 VAC,
colour white on
< 50 mA
Power consumption
< 12 W
Insulation class
II
Overvoltage category
II
Version with DC voltage
Operating voltage (voltage between
colour terminal and terminal „GND“)
24 VDC
Tolerance of operating voltage
± 20%
Current consumption colour white on
< 135 mA
Power consumption
at rated operating voltage
< 4 W
Insulation class
III / II
Marking on name plate
FHF Funke + Huster Fernsig GmbH D-45478 Mülheim a.d. Ruhr
Type: GH5 FHF 10 ATEX 0004 X*) FHF 10 ATEX 0006 X**)
II 3 G Ex nR IIC T6 Gc
II 3 D Ex tc IIIC T85°C Dc
-20°C ≤ Ta ≤ +50°C
Ui = **)........ IP66
Do not open while under power.
After de-energizing, delay X minutes before opening.
Potential electrostatic charging hazard - see instructions.
P/N: ..........................
F-No.: .......................
Month/Year/Tested by
*) Mechanically protected installation
**) Input voltage depending on version.