50
Eaton 93E External Battery Cabinet Installation Manual P-164000057—Rev 05
Number of EBCs
EBC Model
Number of Battery Strings
Runtime
93E 30EBC
3
26
2
93E 30EBC
4
37
93E 30EBC
5
49
93E 30EBC
6
62
1
93E 60EBC
4
14
93E 60EBC
6
26
2
93E 60EBC
8
37
93E 60EBC
10
50
93E 60EBC
12
62
NOTE
Battery times are approximate and vary depending on the load configuration and battery charge.
77..22..33
EEnnvviirroonnm
meennttaall aanndd S
Saaffeettyy S
Sppeecciiffiiccaattiioonnss
Operating Temperature
32°F to 86°F (0°C to 30°C).
Optimal battery performance: 77°F (25°C)
Transit Temperature
-13°F to 140°F (-25°C to 60°C)
Storage Temperature
-13°F to 131°F (-25°C to 55°C)
Recommended battery storage: 59°F to 77°F (15°C to 25°C)
Operating Altitude
Maximum 1500m (5000 ft) at 30°C without derating
Transit Altitude
15000m (49213 ft)
Ventilation
Convection
Relative Humidity (operating and
storage)
5% to 95% maximum noncondensing
Acoustical Noise
Not applicable
Safety Conformance
UL1778 5
th
edition, UL60950-1 1
st
edition
Agency Markings
cULus
EMC (Class A)
FCC Part 15 Class A and 62040-2 c3
Содержание 93E 30EBC
Страница 1: ...p n P 164000057 Revision 05 30EBC and 60EBC Installation Manual Eaton 93E External Battery Cabinet...
Страница 6: ...vi Eaton 93E External Battery Cabinet Installation Manual P 164000057 Rev 05 List of Figures...
Страница 8: ...viii Eaton 93E External Battery Cabinet Installation Manual P 164000057 Rev 05 List of Tables...
Страница 30: ...22 Eaton 93E External Battery Cabinet Installation Manual P 164000057 Rev 05 Installation Plan and Unpacking...
Страница 54: ...46 Eaton 93E External Battery Cabinet Installation Manual P 164000057 Rev 05 Onelines and Schematics...
Страница 60: ...P 16400005705 P 164000057 05...