EAE Technology
www.eaetechnology.com
Page 11 / 21
Product Manual MD
100
EAE KNX Presence Detector
MD
100
PM R
1.0
17
Group 1 - output
Switch light
DPT 1.001
1 bit
CRT
This object is always available. “Switch light” object must be linked with the switching object of the actuator
used in conjunction with Group 1-lighting for switching ON and OFF. It is possible to request the switching
status from the detector.
18
Group 1 - output
Dimming level
DPT 5.001
8 bit
CRT
This object is only visible if the "Operating mode" parameter is set to "constant light control" in the Constant
light level" parameter window.
This object must be linked with dimming-level object of the actuator used for dimming lighting group 1.
“Group 1 – input Dimming level” object can increase/decrease the output of this object according to
parameters.
19
Group 1 - input
Switch light
DPT 1.001
1 bit
CW
This object is always available. It must be linked with switching object of button that enables a room user to
control lighting group 1.
Receiving a telegram through this object has an alterable behaviour according to “Light level control”
parameter in the “Constant light level” parameter window.
Disable constant light and dim:
It remains disabled until detector itself ascertains no person is left in the
room, re-enables the constant light control and switches the lighting OFF.
Don’t disable and no action:
No action receiving a telegram through Group 1 - input object.
20
Group 1 – input
Dimming level
DPT 5.001
8 bit
CW
This object is only visible if the "Operating mode" parameter is set to "Constant light control" in the
Constant light level" parameter window.
Lighting groups which are linked to dimming output of Group 1 can be dimmed to brightness level by this
object.
Receiving a telegram through this object has an alterable behaviour according to “Light level control”
parameter in the “Constant light level” parameter window.
Disable constant light and dim:
It remains disabled until detector itself ascertains no person is left in the
room, re-enables the constant light control and switches the lighting OFF.
Don’t disable and no action:
No action receiving a telegram through Group 1 - input object.
21
Group 1 – input
Dimming light
DPT 3.007
4 bit
CW