EAE Technology
www.eaetechnology.com
Page 9 / 21
Product Manual MD
100
EAE KNX Motion Detector
MD
100
PM R
1.0
8
Presence
Lighting stay ‘ON’
time
DPT
5.005
8 bit
CRW
This object is only visible if the "Switch-on delay and stay-on time change by bus" parameter is set
to "yes" in the "Presence" parameter window.
This object is used to receive Lighting stay-on time (in seconds) by the bus. Detector sends “on”
telegram via presence output object at detected movement and stays “ON” until the adjusted
time runs out.
10
Brightness
Measured value
DPT
9.004
16 bit
CRT
This object is only visible if the "Enable brightness" parameter is set to "yes" in the "General"
parameter window.
“Measured value” can be send to the bus “on change or/and cyclically” by this object.
11
Brightness
Calibration
DPT
9.004
16 bit
CRW
This object is only visible if the "Enable brightness" parameter is set to "yes" in the "General"
parameter window.
For an optimum function of constant light control a calibration of the sensor for brightness
detection is required. Current brightness value of detection range of the sensor must be written
to calibration object as a new lux value. Sensor will calculate the calibration factor according to
new lux value automatically. Subsequent detections will be calculated with new calibration factor.
12
Constant Light
External Brightness
DPT
9.004
2 byte
CRW
This object is only visible if the "Used brightness" parameter is set to "external" in the "Constant
light level" parameter window.
External brightness object is used to receive brightness value for constant light control from an
external daylight sensor.
13
Constant Light
Set point value
DPT
9.004
2 byte
CRW
This object is only visible if the "Set point type" parameter is set to "with parameter and object"
in the "Constant light level" parameter window.
Set point value for constant light level control can be written to this object. Any value received
outside the permissible range of 10…1000 lux will be exchange to closest limit value.
14
Constant Light
Switch ‘ON’ delay
DPT
5.005
1 byte
CRW
This object is only visible if the "ON times change by bus" parameter is set to "yes" in the
"Constant light level - Lighting" parameter window.
After a detection, sensor waits to start constant light level until “Switch ON delay time” is expired.
Current “Switch On delay time” can be read from the object or a new “Switch on delay time” can
be written to the object. Any value received outside the permissible range of 0…30 is rejected.