Product Manual MD

 

100

 

 

 

EAE KNX Presence Detector 

 

 

 

 

 

 

 

MD

 

100

 

 PM R

 

1.0

 

 

 

Used brightness 

 

*internal 

  

external

 

 

 

 

This parameter determines that brightness val 
internal or external.   

ue which is used for constant light con trol will be  

Maximal variation from set point value 

 

  15 lux 

 

*30 lux 

 

  45 lux 

 

  60 lux  

 

 

This parameter is used to adjust hysteresis value for set point value. (-30…set point value…+30) 

Dimming level is only sent by “dimming level” object if current brightness value is out of the range 
specified with maximal variation of set point value.  

Max step size for dimming 

 

  0.5%   
1% 

 

  1.5%   
2%  
  2.5%   
3%  

*5% 

 

 

 

This parameter is used to select step size dimming for constant light control. “Dimming level” object 

sends the dimming values (1 byte) with selected step size to reach the appropriate brightness in the 
room for set point value. (%100, %95, % 90 etc.)  

Transmit next dimming value after 

 

  0.5s 

 

*1s 

 

  2s  
  3s  
  5s

 

 

 

 

This parameter is used to specify the time interval between two sending dimming value. After 

sending a dimming value (%60), next dimming value (%55) will be sent after the time interval 
selected.   

Finish constant light level control with  

 

*only dimming value telegram 

  

switching off 

 

 

 

This parameter defines the way in which constant light level control will end.  

Only dimming value telegram: If there is sufficient ambient light in a room, constant light level 

control is ended by only dimming value telegram.  

Switching off: If there is sufficient ambient light in a room, constant light level control is ended by 

switch (OFF) telegram.  

Lighting group X offset to dimming level 
for group 1 

 

-100…

*0

…100

 

 

This parameter is used to express offset value of additional Lighting Group X (X: 2, 3, and 4) according 

to “Lighting Group 1”. An offset parameter will be created for every additional lighting group.  

Lighting level control 

 

*disable constant light and dim 

  

don’t disable and no action

 

 

Содержание MD100

Страница 1: ...EAE KNX Motion Detector Product Manual MD100 Order Number 48018...

Страница 2: ...t 1 General 2 1 1 Technical Data 2 1 2 Operation and Display 4 1 3 Scale Drawings 5 2 Communication Object Information 6 2 3 Communication Object Table 6 2 4 Communication Object Description 8 3 Param...

Страница 3: ...er movement no action Stay on time can be changed the by end user Air conditioning and ventilation systems can be controlled by independent HVAC channel Presence information can be sent to presence mo...

Страница 4: ...guideline and low voltage Application program Communications objects Number of addresses max 44 255 NOTE Device default physical address is 15 15 255 In order to configure KNX Motion detector ETS app...

Страница 5: ...r in meter of the different areas for different installation heights M Detection range 1 2 Operation and Display Figure 1 Surface mounted MD 100 Table 1 Motion M A B C D 5 0m 12 18 3 0 4 0m 10 15 2 3...

Страница 6: ...hnology com Page 5 21 Product Manual MD100 EAE KNX Motion Detector MD100 PM R1 0 Figure 2 Flush mounted MD100 1 KNX connection terminal 2 Programming button 3 Blue movement LED 1 3 Scale Drawings Figu...

Страница 7: ...Flags 0 General In operation DPT 1 002 1 bit CWT 1 General Presence slave 1 DPT 1 001 1 bit CRW 2 General Presence slave 2 DPT 1 001 1 bit CRW 3 General Presence slave 3 DPT 1 001 1 bit CRW 4 General...

Страница 8: ...24 Group 2 output Dimming level DPT 5 001 8 bit CRT 25 Group 2 input Switch light DPT 1 001 1 bit CW 26 Group 2 input Dimming level DPT 5 001 8 bit CW 27 Group 2 input Dimming light DPT 3 007 4 bit C...

Страница 9: ...tion objects by master sensor Slave sensors send the value 1 when movement is present otherwise send value 0 These values are processed in OR gate by master sensor If the output value is 1 master sens...

Страница 10: ...ue Sensor will calculate the calibration factor according to new lux value automatically Subsequent detections will be calculated with new calibration factor 12 Constant Light External Brightness DPT...

Страница 11: ...to output object at detected movement and stays ON until t adjusted time runs out Current Lighting stay ON time can be read from the object or a new Lighting stay ON time can be written to the object...

Страница 12: ...ng a telegram through this object has an alterable behaviour according to Light level control parameter in the Constant light level parameter window Disable constant light and dim It remains disabled...

Страница 13: ...re enables the constant light control and switches the lighting OFF Don t disable and no action No action receiving a telegram through Group 1 input object 3 Parameters Parameters chapter describes E...

Страница 14: ...ble HVAC no yes Parameter enables brightness parameters and objects Overwrite settings for download yes no This parameter is used to decide whether settings stated below are overwritten or not by down...

Страница 15: ...ter detecting first movement Detector waits for selected number of movements during Presence switch ON delay time in order to send that the presence information is ON Presence stay ON time sec 1 10 25...

Страница 16: ...d with the value 0 and re enabled with value 1 Behaviour disable lighting no action Light ON Light OFF This parameter is used for selecting whether to send a telegram from the presence output object b...

Страница 17: ...ration factor This parameter is used select calibration method of the brightness sensor inside the detector There are two options in order to calibrate the brightness sensor Via object Calibration val...

Страница 18: ...rightness on off control Lighting groups are only controlled by switch object according to set point value If measured brightness value is greater than the set point value switch object is set to the...

Страница 19: ...point value 100 95 90 etc Transmit next dimming value after 0 5s 1s 2s 3s 5s This parameter is used to specify the time interval between two sending dimming value After sending a dimming value 60 nex...

Страница 20: ...f lighting Automatically ON and OFF Lighting group is controlled automatically by detector according to presence information If person is present in the room ON command is sent to the lighting group i...

Страница 21: ...value OFF and enabled with the value ON Behaviour disable lighting no action Light ON Light OFF This parameter is used for selecting whether a telegram is sent to lighting group before disabling ligh...

Страница 22: ...d Stay ON time objects are not visible Disable light level control no ON for disabling OFF for enabling OFF for disabling ON for enabling This parameter determines the value type for disabling enablin...

Страница 23: ...etechnology com Page 22 21 Product Manual MD100 EAE KNX Presence Detector MD100 PM R1 0 Light ON After enabling the HVAC output it is set to the value ON Light OFF After enabling the HVAC output it is...

Отзывы: