Settings
52
© 2017 DynaGen Technologies Inc
TOUGH Series Manual
Name
Parent Menu
Range
Description
Auto Idle Link
Timers > Engine Logic
Disable,
Breaker Trip
If set to breaker trip, the breaker trip will be
activated whenever the controller is in the Idle
mode. The breaker trip will be turned off when
Idle mode is exited if it was not in the latched
state.
If the user delaches the breaker trip output while
auto idle is active the breaker trip will turn off for
one section and then turn back on.
4.5.1.4.2 Idle Inhibit
Use this feature to prevent start up when the Idle mode switch is active.
Settings (Other Config > Idle Inhibit, in the Configuration Software these are under the switched inputs when the idle input is
enabled.)
Name
Range
Description
Remote Start (Start /
Stop Switched Input
Inhibit)
Enable
Disable
Prevent the remote start switch input from starting the engine when the idle
switch is active.
Aux Start (Aux 1,2,3,4
Sensor Autostart Inhibit)
Enable
Disable
Prevent Auxiliary 1, 2, 3, and 4 sensors autostart feature from starting the
engine when the idle switch is active.
If the engine is in the IDLE mode because of the
feature, the remote start (start/stop) and auxiliary sensors autostart
can still start the engine.
This prevents starting when the Idle switch is active in the AUTO mode. This will also shutdown the engine if the idle switched input
is activated when the controller is in the delay-to-start, preheat, cranking, and crank reset states. The main purpose is to prevent a
remote start if the idle switch was accidentally left on.
4.5.2
Schedulers
Enter topic text here.
4.5.2.1 Exerciser
The Exerciser function is used to start and run the engine periodically. The following settings configure the Exerciser function.
Exerciser Settings
(in Timers menu)
Name
Range
Description
Enable
Enable ~ Disable
Enables the exerciser feature.
Delays -> Pre-Alarm
1 ~ 20 minutes
Amount of time to display a warning before starting the engine.
Delays -> Run Time
10 ~ 1500 minutes
Amount of time to run the engine.
Schedule -> Start Date
1 ~ 31
The day of the month and the time for the first exerciser run.
This setting is only used to set the first exerciser run. All
subsequent exerciser runs use the Repeat Days setting to
determine when they should run.
If the date and hour selected is already in the past for the
current month then the exerciser will be started on the next
month with that date and hour. Also if the date is not yet in the
past but the current month does not have that date (e.g.
February 21 and a date of 31 is selected) the exerciser will run
on the next month to have that date (e.g. 31rst of March) at the
hour specified.
Schedule -> Start Hour
0 ~ 23
Содержание TG410
Страница 4: ...3 2017 DynaGen Technologies Inc TOUGH Series Manual User Guide ...
Страница 11: ...Installation 10 2017 DynaGen Technologies Inc TOUGH Series Manual 2 3 Wiring Harnesses ...
Страница 12: ...Installation 11 2017 DynaGen Technologies Inc TOUGH Series Manual 2 4 Typical Wiring Diagram ...
Страница 13: ...Installation 12 2017 DynaGen Technologies Inc TOUGH Series Manual 2 5 Typical Wiring Diagram with RelayPak ...
Страница 17: ...Installation 16 2017 DynaGen Technologies Inc TOUGH Series Manual ...
Страница 20: ...Installation 19 2017 DynaGen Technologies Inc TOUGH Series Manual ...
Страница 22: ...Installation 21 2017 DynaGen Technologies Inc TOUGH Series Manual ...
Страница 40: ...Settings 39 2017 DynaGen Technologies Inc TOUGH Series Manual ...