Settings
30
© 2017 DynaGen Technologies Inc
TOUGH Series Manual
Name
Active Mode
Description
Warmup
Warmup Timer
Active after Warmup timer has expired to apply load to engine.
Cooldown
Cooldown Timer
Active when Cooldown timer is active.
Engine Running
Running
Active after crank success.
Exercising
Exercise Timer
Active during the engine exercising cycle.
Batt. Recharge (Battery
Recharge)
Battery Recharge
Timer
Active during the battery recharge cycle.
Maintenance
(Maintenance Required)
Global
Active when Maintenance timer has expired. If the timer has expired when the
controller is in the RUN mode the output does not turn on until the controller
enters the OFF or AUTO mode. See the
LowBat InCrank (Low
Battery During Cranking)
Cranking
Active when Low Battery During Cranking warning is displayed.
Aux Sensor 1
Auxiliary Settings
Dependent
Active dependent upon settings in the
sensor section.
Aux Sensor 2
Aux Sensor 3
Aux Sensor 4
Force Regen
User Controlled
When user triggers a Force Regeneration, output is active for 20 seconds
then switches off.
Regen Inhibit
User Controlled
When user triggers a Regeneration Inhibit, output is active for 20 seconds
then switches off.
Common Failure
Any Failure
Active when any failure occurs.
RPM Increment
Running
Output is used to to trigger inputs on an ECM to control speed. See
RPM Decrement
Running
Output is used to to trigger inputs on an ECM to control speed. See
DEF Fluid Pump
Running
Active when DEF Fluid Level falls below the DEF Low Level and stays active
until the level rises above the DEF High Level. See
for more information.
Genset Disable
Global
Disables the generator during a stationary Regen on Kubota engines (see
Aftertreatment in the J1939 User Manual ) or also during an engine IDLE
condition from the IDLE switched input. Automatic idle is ignored. If the
generator voltage is not below the under voltage setpoint in 10s, the controller
will shut down the engine on "Generator Disable Failure."
Dummy Load
Running
Output is controlled by the
feature.
Breaker Trip
Running
Output is controlled by the
features and by the
feature.
Auto Idle
Warm-up, Cooldown
Active when the warm-up or cooldown idle is active. See Warm-up Idle and
Cooldown Idle in
. This does to react to the Idle switched input.
Warning Functions
Functions
Low Engine Temperature
High Engine Temperature
Low Oil Pressure
Under Speed
Over Speed
Low Fuel Level
High Fuel Level
Low Battery Voltage
High Battery Voltage
Under Frequency
Over Frequency
AC Under Voltage
AC Over Voltage
Over Current
Fuel In Basin
Battery Charger Fault
Configurable Warning 1
Configurable Warning 2
Auxiliary Sensor 1
Auxiliary Sensor 2
Auxiliary Sensor 3
Auxiliary Sensor 4
Содержание TG410
Страница 4: ...3 2017 DynaGen Technologies Inc TOUGH Series Manual User Guide ...
Страница 11: ...Installation 10 2017 DynaGen Technologies Inc TOUGH Series Manual 2 3 Wiring Harnesses ...
Страница 12: ...Installation 11 2017 DynaGen Technologies Inc TOUGH Series Manual 2 4 Typical Wiring Diagram ...
Страница 13: ...Installation 12 2017 DynaGen Technologies Inc TOUGH Series Manual 2 5 Typical Wiring Diagram with RelayPak ...
Страница 17: ...Installation 16 2017 DynaGen Technologies Inc TOUGH Series Manual ...
Страница 20: ...Installation 19 2017 DynaGen Technologies Inc TOUGH Series Manual ...
Страница 22: ...Installation 21 2017 DynaGen Technologies Inc TOUGH Series Manual ...
Страница 40: ...Settings 39 2017 DynaGen Technologies Inc TOUGH Series Manual ...