Settings
64
© 2017 DynaGen Technologies Inc
TOUGH Series Manual
4.7.2
MOD Bus (RS485)
The Modbus functionality on the controller provides interface ability to PLCs, SCADA and building management systems. For
detailed information about the Modbus registers and their interpretations please use the Modbus Reference Manual. The manual
can be found at
.
Name
Description
Range / Values
Device Address
The device address of the controller.
1 ~ 247 (Default = 1)
Baud Rate (BPS)
The speed at which the controller (slave)
communicates with the master.
9600 (Default), 19200, 38400, 57400
Communication Protocol
The controller always communicates in
Modbus RTU.
Modbus RTU (Fixed)
Slave / Master Configuration
The controller is always the slave and must
be queried by the master.
Slave (Fixed)
4.8
Other Config
This section contains miscellaneous settings.
4.8.1
Password
The default password to change settings is "0000". The Password menu is used to change this password and control when it
shows up.
Other Config > Passcode:
Name
Range
Description
Bypass
Disable (Default)
Enable
If enabled a password is not required to change settings.
Timeout
0 ~ 120 minutes in 1
minute increments
(Default = 10 minutes)
How long after the password is entered before the user is
required to enter it again.
The timeout is implemented as a simple countdown timer. The
following apply:
·
If the bypass time is changed this new bypass time will not
be loaded until the countdown timer has expired and the
user enters the password.
·
The countdown timer is stored in non-volatile memory and is
"paused" when the controller is powered off. The counter will
resume when the controller is powered on again.
·
Any button press in the menu will reset the timer.
Passcode
0000 ~ 9999 (Default =
0000)
The four numeric digits that make up the password.
4.8.2
Settings Name
If storing settings from the RapidCore Configuration Software a custom name can be entered to allow users to determine the
settings that are stored in the controller. This custom name, called "Configuration Name" (ID in the controller) is found under
Options in the settings tab of the Configuration Software. There is no controller menu to set this ID. It can be up to 12 characters
long.
The Configuration Name can be viewed in the Device Info > About TG410/TG350 menu. It is labeled ID.
Содержание TG410
Страница 4: ...3 2017 DynaGen Technologies Inc TOUGH Series Manual User Guide ...
Страница 11: ...Installation 10 2017 DynaGen Technologies Inc TOUGH Series Manual 2 3 Wiring Harnesses ...
Страница 12: ...Installation 11 2017 DynaGen Technologies Inc TOUGH Series Manual 2 4 Typical Wiring Diagram ...
Страница 13: ...Installation 12 2017 DynaGen Technologies Inc TOUGH Series Manual 2 5 Typical Wiring Diagram with RelayPak ...
Страница 17: ...Installation 16 2017 DynaGen Technologies Inc TOUGH Series Manual ...
Страница 20: ...Installation 19 2017 DynaGen Technologies Inc TOUGH Series Manual ...
Страница 22: ...Installation 21 2017 DynaGen Technologies Inc TOUGH Series Manual ...
Страница 40: ...Settings 39 2017 DynaGen Technologies Inc TOUGH Series Manual ...