Settings
34
© 2017 DynaGen Technologies Inc
TOUGH Series Manual
Name
Range
Description
Setpoints > Low Warn (Low Warning) Disabled, 32 ~ 200°F (0
~ 93.3
0
C)
Reading at which a "Low Engine Temp" warning occurs.
Displays 'Low Engine Temp' on the screen. Only applies if
Sensor Type has been set to a sender. Monitored globally
including OFF and AUTO.
Setpoints > High Warn (High
Warning)
Disabled, 50 ~ 300°F
(10 ~ 148.9
0
C)
Reading at which a "High Engine Temp" warning occurs. Only
applies if Sensor Type has been set to a sender. Only
monitored in the RUN mode.
Setpoints > High Fail (High Failure)
Disabled, 50 ~ 300°F
(10 ~ 148.9
0
C)
Reading at which a "High Engine Temp" failure occurs. Only
applies if Sensor Type has been set to a sender. Only
monitored in the RUN mode.
Note: All temperature settings are entered in terms of Fahrenheit.
4.4.2
Oil Pressure
Use the following settings' configurations to allow the controller to read and interpret data from the oil pressure sensor or switch.
Name
Range
Description
Signal Source
Port A
Port B
Port C
Port D
J1939 Bus*
The sensor input pin where the oil pressure switch or sender is
attached.
*Oil pressure is obtained from the engine controller (ECM)
using the CANbus communication port and J1939 protocol.
Sensor Type
DAT 100P/R240*
VDO 150P/R180*
(custom sender)**
Close = Warning
+
Open = Warning
+
Close = Failure
+
Open = Failure
+
Select the sender that is connected to the Signal Source
above. If using a switch select the action that should occur
when the switch is active.
*These are preprogrammed into the controller and cannot be
changed.
- DAT 100P/R240 supports the Stewart - Warner 279B-F and
Datcon 2505-00 sender tables.
- VDO 150P/R180 supports the VDO 360-004 oil pressure
sender.
DAT 100P/R240 and VDO 150P/R180 can not be used on port
A. To use on port A store as a custom sender table using the
RapidCore Configuration software.
**A custom table created using the RapidCore Configuration
Software. The text (custom sender) will be replaced with the
custom text you choose when creating the sender.
+
The switch must close to ground.
Trim Offset
-50.0 ~ 50.0 PS (-344.7
~ 344.7kPa)
Calibrate a sensor by using the offset to correct errors. Only
applies if Sensor Type has been set to a sender.
Setpoints -> Bypass Time
0 ~ 90 seconds
Amount of time to bypass warnings and failures after engine
has started.
Setpoints -> Low Warning
Disabled, 0.1 ~ 99.0 psi
(0.7 ~ 682.6kPa)
Reading at which a "Low Oil Pressure" warning occurs. Only
applies if Sensor Type has been set to a sender.
Setpoints -> Low Failure
Disabled, 0.1 ~ 99.0 psi
(0.7 ~ 682.6kPa)
Reading at which a "Low Oil Pressure" failure occurs. Only
applies if Sensor Type has been set to a sender.
Note: All pressure settings are entered in terms of psi.
Содержание TG410
Страница 4: ...3 2017 DynaGen Technologies Inc TOUGH Series Manual User Guide ...
Страница 11: ...Installation 10 2017 DynaGen Technologies Inc TOUGH Series Manual 2 3 Wiring Harnesses ...
Страница 12: ...Installation 11 2017 DynaGen Technologies Inc TOUGH Series Manual 2 4 Typical Wiring Diagram ...
Страница 13: ...Installation 12 2017 DynaGen Technologies Inc TOUGH Series Manual 2 5 Typical Wiring Diagram with RelayPak ...
Страница 17: ...Installation 16 2017 DynaGen Technologies Inc TOUGH Series Manual ...
Страница 20: ...Installation 19 2017 DynaGen Technologies Inc TOUGH Series Manual ...
Страница 22: ...Installation 21 2017 DynaGen Technologies Inc TOUGH Series Manual ...
Страница 40: ...Settings 39 2017 DynaGen Technologies Inc TOUGH Series Manual ...