Settings
55
© 2017 DynaGen Technologies Inc
TOUGH Series Manual
NOTE
: The maintenance timer displays "Service Required" when this time expires. This message is only displayed the next time
the controller enters the RUN mode. If the timer expires when the controller is in the RUN mode the message is not displayed.
4.6
AC Monitor
The controller has the ability to monitor AC voltage and current from a generator. The following sections are used to configure
settings associated with AC monitoring.
4.6.1
Generator Voltage
The following settings are used to configure the controller's response to voltage measurements.
(AC Monitor > Genset Voltage menu)
Name
Range
Description
Voltage Source
Disable
2-Wire Single
3-Wire Single
3-Wire 3-Phase
4-Wire 3-Phase
4-Wire Delta
Auto Selection
The wiring configuration of the generator. Disable will disable
AC voltage and AC frequency sensing and display.
2-Wire Single: One 120VAC L-N. Use phase A.
3-Wire Single: 120/240VAC systems. Use phases A and B.
3-Wire 3-Phase: Three phase delta without a ground.
4-Wire 3-Phase: Three phase Wye system. Center taped
ground.
4-Wire Delta: Delta with a ground. The high leg is phase B. For
example if A-N and C-N read 120VAC then B-N will read
208VAC.
Selecting Auto Selection will use the
switched
inputs to determine the wiring configuration.
This setting also enables the
display.
Scaling Factor
0.500 ~ 2.500
The gain to apply to the AC voltage that is read at the
controller. See below for more information.
Nominal Volts
50 ~ 800 VAC*
Generator voltage output when operating under normal running
conditions.
Auto Nominal > 1Ph 3-Wire (1-Phase
3-Wire)
50 ~ 800 VAC*
Nominal Volts when using the
inputs.
Auto Nominal > 3-Phase (1)
50 ~ 800 VAC*
Auto Nominal > 3-Phase (2)
50 ~ 800 VAC*
Auto Nominal > 3-Phase (3)
50 ~ 800 VAC*
Auto Scaling > 1Ph 3-Wire (1-Phase
3-Wire)
0.500 ~ 2.500
Scaling Factor when using the
Auto Scaling > 3-Phase (1)
0.500 ~ 2.500
Auto Scaling > 3-Phase (2)
0.500 ~ 2.500
Auto Scaling > 3-Phase (3)
0.500 ~ 2.500
Auto Single
A-C Phase
A-B Phase
For 1-Phase 3-Wire when using the
This determines which phases the single phase voltage is read
from.
Setpoints > Low Warn
50 ~ 99%
Reading at which a warning occurs.
Setpoints > Low Fail
50 ~ 99%
Reading at which a failure occurs.
Setpoints > High Warn
101 ~ 150%
Reading at which a warning occurs.
Setpoints > High Fail
101 ~ 150%
Reading at which a failure occurs.
*NOTE
: 800 VAC applies to software logic only. Do not exceed 600 VAC on the AC Voltage terminals including
during over voltage warning and failure conditions.
Содержание TG410
Страница 4: ...3 2017 DynaGen Technologies Inc TOUGH Series Manual User Guide ...
Страница 11: ...Installation 10 2017 DynaGen Technologies Inc TOUGH Series Manual 2 3 Wiring Harnesses ...
Страница 12: ...Installation 11 2017 DynaGen Technologies Inc TOUGH Series Manual 2 4 Typical Wiring Diagram ...
Страница 13: ...Installation 12 2017 DynaGen Technologies Inc TOUGH Series Manual 2 5 Typical Wiring Diagram with RelayPak ...
Страница 17: ...Installation 16 2017 DynaGen Technologies Inc TOUGH Series Manual ...
Страница 20: ...Installation 19 2017 DynaGen Technologies Inc TOUGH Series Manual ...
Страница 22: ...Installation 21 2017 DynaGen Technologies Inc TOUGH Series Manual ...
Страница 40: ...Settings 39 2017 DynaGen Technologies Inc TOUGH Series Manual ...