Settings
49
© 2017 DynaGen Technologies Inc
TOUGH Series Manual
Name
Range
Description
Cooldown Time
0 ~ 600 s in 5 s
increments
Amount of time to cool down the engine after a stop command
has been received. During this time the Warmup output turns
off and the Cooldown output turns on. If another start command
is received during cool down, the controller will return to running
mode.
ETS On Duration (Energize to Stop)
0 ~ 30 seconds
Amount of time the Energize to Stop output is on after the
engine has shut down. If controller still detects speed (RPM)
after this time expires, it goes to a
' failure. Time
must be greater than 0 seconds for the Energize to Stop
function to work.
Warm-up Idle
Idle during warm-up option. See the
Idle Settings
Cooldown Idle
Auto Idle Link
4.5.1.1 Preheat Mode
The controller has the ability to control the length of the preheat time through 3 different methods. The table below describes each
method:
Preheat Mode Setting (Timers > Engine Logic menu)
Mode
Description
Preheat Timer
This mode uses the Preheat Time setting in the Engine Logic menu.
Switched Input
This mode uses a switched input set to 'ECM Preheat' to determine when to exit
preheat.
The preheat time (in
) must be set to a minimum of 5 seconds for this
input to work. If the switched input is or becomes active when the preheat timer is
counting down the controller displays 'ECM Preheating' on the screen after the
preheat counter has finished its countdown. Cranking begins when the 'ECM
Preheat' switched input is no longer active.
J1939
This mode uses commands sent from the ECM over J1939 to decide when to exit
preheat.
NOTE
: During preheat the Glowplug switched output is on (it needs to be set to a switched output -- see
).
4.5.1.2 False Restart
The false restart feature is used to monitor and recover from unsuccessful crank attempts where the speed did go above the crank
disconnect and the controller is in the RUN mode. For example the engine might have stalled shortly after cranking.
False Restart settings (under Timers > Engine Logic menu)
Name
Range
Description
False Restart (Restart on False
Start)
Enable
Disable
Determines if the controller will monitor for false starts and
attempt a restart. Controller will only attempt restarting the
engine as many times as determined by Crank Attempts.
False Check (False Restart Detect
Time)
5 ~ 30 in 1 second
intervals
Amount of time after successful cranking to monitor for a false
restart. A false restart is defined as the speed dropping below
250 RPM for 2 seconds. If this time expires and the engines
stalls out, the controller will not attempt a restart.
This time starts from crank success.
Tip: It takes up to 2 seconds for the false restart to be triggered. In addition it takes time for the engine speed to drop below
250RPM. These should be measured and added to the desired False Check setting.
Содержание TG410
Страница 4: ...3 2017 DynaGen Technologies Inc TOUGH Series Manual User Guide ...
Страница 11: ...Installation 10 2017 DynaGen Technologies Inc TOUGH Series Manual 2 3 Wiring Harnesses ...
Страница 12: ...Installation 11 2017 DynaGen Technologies Inc TOUGH Series Manual 2 4 Typical Wiring Diagram ...
Страница 13: ...Installation 12 2017 DynaGen Technologies Inc TOUGH Series Manual 2 5 Typical Wiring Diagram with RelayPak ...
Страница 17: ...Installation 16 2017 DynaGen Technologies Inc TOUGH Series Manual ...
Страница 20: ...Installation 19 2017 DynaGen Technologies Inc TOUGH Series Manual ...
Страница 22: ...Installation 21 2017 DynaGen Technologies Inc TOUGH Series Manual ...
Страница 40: ...Settings 39 2017 DynaGen Technologies Inc TOUGH Series Manual ...