TOUGH Series Manual
4.6.3.4 Dummy Load
The dummy load feature can be enabled to prevent wet stacking.
AC Monitor > Genset Current > Dummy Load:
Name
Range
Description
Bypass Time
Disabled, 1 ~ 120
seconds
The amount of time to delay before applying the dummy load.
Load On
Disabled, 1 ~ 500A
The threshold below which the dummy load is applied. There is
a 4s debounce time. The bypass time must expire before the
load is applied. All phases must drop below this threshold to
trigger dummy load.
Load Off
Disabled, 1 ~ 500A
The threshold above which the dummy load is removed.
Dummy load is turned off if one phase rises above this
threshold.
One of the
must also be set to dummy load. The output is only turned on when the engine is running.
4.6.3.5 EPS Supplying Load
The EPS (Emergency Power System) Supplying load sets a flag in Modbus register 40006 to indicate to the DynaGen RA400
remote annunciator that the generator is actively supplying power. If this flag is set the RA400 will light it's EPS Supplying Load
indicator. This is used to meet NFPA110 requirements.
If the actual current measured on any one phase of the generator is above 5% of the AC over current warning set point then the
EPS Supplying load flag is set. For more information on this register refer to the Tough Series modbus manual or RA400 manual.
4.7
Communications
The controller has the ability to communicate with other systems over communication buses. The following sections relate to
settings associated with communications.
4.7.1
CAN Bus (J1939)
For detailed information about J1939 settings and functions please use the J1939 Reference Manual. The manual can be found at
Name
Range
Description
ECM Model
Generic J1939
John Deere JDEC
Volvo EMS
This is not a complete
list. See the J1939
User Manual for the full
list.
Choose one of the compatible ECM modules from the list.
ECM Communication Failure
Enable ~ Disable
If no CAN messages are received for more than 6 seconds, the
controller shuts down the engine.
DTC Display
Enable ~ Disable
Enables or disables active fault messages (DM1) monitoring.
Active DTC Log
Enable ~ Disable
Enables or disables the storing of active faults (DM1).
Read Stored DTC
Enable ~ Disable
Enables or disables the ability to request stored fault codes
from the ECM (DM2).
Auto Power ECM
Enable ~ Disable
When enabled, the fuel relay is enabled in Auto mode so that
the ECM is already booted up and initialized before the user
decides to start the engine.
Содержание TG410
Страница 4: ...3 2017 DynaGen Technologies Inc TOUGH Series Manual User Guide ...
Страница 11: ...Installation 10 2017 DynaGen Technologies Inc TOUGH Series Manual 2 3 Wiring Harnesses ...
Страница 12: ...Installation 11 2017 DynaGen Technologies Inc TOUGH Series Manual 2 4 Typical Wiring Diagram ...
Страница 13: ...Installation 12 2017 DynaGen Technologies Inc TOUGH Series Manual 2 5 Typical Wiring Diagram with RelayPak ...
Страница 17: ...Installation 16 2017 DynaGen Technologies Inc TOUGH Series Manual ...
Страница 20: ...Installation 19 2017 DynaGen Technologies Inc TOUGH Series Manual ...
Страница 22: ...Installation 21 2017 DynaGen Technologies Inc TOUGH Series Manual ...
Страница 40: ...Settings 39 2017 DynaGen Technologies Inc TOUGH Series Manual ...