D.8 COMPRESSOR CONTROLLER
SYMPTOMS OF THE FAULT
The refrigerator is too warm and the compressor does not run
How to Confirm this fault
Measure the voltage at the input terminals of the compressor controller. If the voltage
is more than 11.5 volts (12 volt system) or more than 22.5 volts (24 volts system) the
compressor should run. If the compressor does not run, proceed as follows.
Repair action required
1. Remove the thermostat and compressor fan wires (if fitted). From terminals T, C,
and F of the compressor controller. Fit a temporary wire between terminals T and C.
The compressor should then run.
2. If the compressor does not run, CHECK THE FUSE, in the compressor controller
again as explained on page no 69.
3. If the compressor still does not run, change the compressor controller with another
of the same model (or compressor controller specified by the system supplier) see
page 85.
4. If the compressor still does not run, the compressor controller is NOT
FAULTY.PROCEED TO THE NEXT STEP ON THE FAULT FINDING CHART No.1
Содержание VC150
Страница 1: ......
Страница 3: ...3 SECTION I ...
Страница 4: ...4 ...
Страница 24: ...24 MODULE AND BATTERY WIRING DIAGRAMS SYSTEM WIRING DIAGRAM ...
Страница 25: ...25 SYSTEM WIRING DIAGRAM GENERAL LAYOUT DIAGRAM ...
Страница 26: ...26 GENERAL LAYOUT DIAGRAM ELECTRICAL CIRCUIT DIAGRAM ...
Страница 27: ...27 ELECTRICAL CIRCUIT DIAGRAM REFRIGERATION CIRCUIT DIAGRAM ...
Страница 28: ...28 REFRIGERATION CIRCUIT DIAGRAM ...
Страница 29: ...29 SECTION II ...
Страница 38: ...38 ...
Страница 39: ...39 ...
Страница 42: ...42 ...
Страница 44: ...44 ...
Страница 50: ...50 ...
Страница 124: ...124 ANNEX 1 COMPONENT LAYOUTS OF SOME COMMONLY USED SOLAR REFRIGERATOR ...
Страница 125: ...125 ...
Страница 126: ...126 ...
Страница 127: ...127 ...
Страница 128: ...128 ...
Страница 129: ...129 ...
Страница 130: ...130 ANNEX II ADDITIONAL EPI TOOL KIT NEEDED FOR PHOTOVOLTAIC REFRIGERATOR REPAIR ...
Страница 136: ...136 ...
Страница 137: ...137 ...