81
9. If the compressor runs when you connect the temporary wire, but do not run with
this temporary wire then:
- The thermostat is faulty or
- The wires are incorrectly connected or
- The wires are defective
Repair Action required
1.Tighten, correct or change the wires.
2. If the compressor still does not run CHANGE THE THERMOSTAT in accordance
with the manufacturers instructions.