Installation
12
3.1.4 CONNECTOR D – RELAY OUTPUT E
Terminal Function
Recommended Size
E
13
Relay Output E (NO)
1.0mm² (AWG18)
14
Relay Output E (C)
1.0mm² (AWG18)
15
Relay Output E (NC)
1.0mm² (AWG18)
3.1.5 CONNECTOR E – MAINS L1 MONITORING
Terminal Function
Recommended Size
Ua3 Ua2 Ua1
16
Ua1 (Mains L1)
1.0mm² (AWG18)
17
Ua2 (Mains N, internally connected to Ua3)
1.0mm² (AWG18)
18
Ua3 (Mains N, internally connected to Ua2)
1.0mm² (AWG18)
3.1.6 CONNECTOR F – MAINS L2 MONITORING
Terminal Function
Recommended Size
Ub3 Ub2 Ub1
19
Ub1 (Mains L2)
1.0mm² (AWG18)
20
Ub2 (Mains N, internally connected to Ub3)
1.0mm² (AWG18)
21
Ub3 (Mains N, internally connected to Ub2)
1.0mm² (AWG18)
3.1.7 CONNECTOR G – MAINS L3 MONITORING
Terminal Function
Recommended Size
Uc3 Uc2 Uc1
22
Uc1 (Mains L3)
1.0mm² (AWG18)
23
Uc2 (Mains N, internally connected to Uc3)
1.0mm² (AWG18)
24
Uc3 (Mains N, internally connected to Uc2)
1.0mm² (AWG18)
3.1.8 CONNECTOR H – RELAY OUTPUT A
Terminal Function
Recommended Size
A
25
Relay Output E (NC)
1.0mm² (AWG18)
26
Relay Output E (C)
1.0mm² (AWG18)
27
Relay Output E (NO)
1.0mm² (AWG18)
3.1.9 CONNECTOR I – RELAY OUTPUT B
Terminal Function
Recommended Size
B
28
Relay Output E (NC)
1.0mm² (AWG18)
29
Relay Output E (C)
1.0mm² (AWG18)
30
Relay Output E (NO)
1.0mm² (AWG18)
3.1.10 CONNECTOR J – RELAY OUTPUT C
Terminal Function
Recommended Size
C
31
Relay Output E (NC)
1.0mm² (AWG18)
32
Relay Output E (C)
1.0mm² (AWG18)
33
Relay Output E (NO)
1.0mm² (AWG18)
Содержание DSEP100
Страница 14: ...Installation 14 3 2 2 MAINS BREAKER AND GENERATOR COMMON BUS BREAKER...
Страница 15: ...Installation 15 3 2 3 ALTERNATE TOPOLOGY WIRING DIAGRAMS...
Страница 41: ...This Page is Intentionally Blank...