Specifications
7
2.5 DIGITAL INPUTS
Number
5 inputs each with fixed function
Polarity
Configurable
Arrangement
Contact between terminal and battery negative
Low Level Threshold
2.1 V minimum
High Level Threshold
6.6 V minimum
Maximum Input Voltage
+50 V DC with respect to battery negative
Minimum Input Voltage
-24 V DC with respect to battery positive
Contact Wetting Current
7 mA
Open Circuit Voltage
12 V DC typical
2.6 MAINS VOLTAGE / FREQUENCY SENSING
Measurement Type
True RMS conversion
Supported Topologies
2 phase 3 wire L1-L2.
2 phase, 3 wire L2-L3.
3 phase, 3 wire.
3 phase, 4 wire.
3 phase, 4 wire Delta.
Single phase, 2 wire.
3 phase, 3 wire NVD.
Sample Rate
5 kHz
Harmonics
Up to 25th
Input Impedance
600 k
Ω
between terminals.
Hardware Ranges
576 V ac / 288 V ac between terminals depending on range
selected.
Resolution
1V AC
Voltage Accuracy
±1% of full scale
Phase Measurement Accuracy
±0.5°
Minimum Frequency
3.5 Hz
Maximum Frequency
75.0 Hz
Frequency Resolution
0.01 Hz
Frequency Accuracy
±0.05 Hz
2.7 RELAY OUTPUTS
Number
5 configurable outputs
Polarity
Configurable
Arrangement
Volt-Free single pole changeover contacts
Rated Load
8 A at 250 VAC, 5 A at 30 VDC
Maximum Switching Voltage
250 VAC, 30 VDC
Maximum Switching Current
8 A