DSE Model 7560 ATS and Mains Controller Operators Manual
057-017 7560 OPERATING MANUAL ISSUE 10.2 10/02/09 AM 49
7.6 RUNNING EDITOR
7.6.1 ACCESSING THE ‘RUNNING’ CONFIGURATION EDITOR
•
The ‘running’ editor can be entered while the engine is running. All protections remain active if the engine is running while
the running editor is entered.
•
Press and hold the
button to enter the running editor.
EDITING A PARAMETER
•
Enter the editor as described above.
•
Press the left
or right
buttons to cycle to the section you wish to view/change.
•
Press the up
or down
buttons to change the parameter to the required value.
•
To save paremeters scroll to `save changes and exit followed by the down
buttton
•
To cancel changes scroll to `Abandon changes and exit followed by the down
button
ADJUSTABLE PARAMETERS (Running editor)
Running Editor
Section
Parameter as shown on display
Factory Settings
DISPLAY Contrast
l
Language
English
Load power factor
%
Load parallel power
%
Enable commissioning screens
No
Voltage adjust
(manual mode only engine running bus breaker open)
Raise Steady Lower
Frequency adjust
(manual mode only engine running bus breaker open)
Raise Steady Lower
Enable mains decoupling
No
Abandon changes and exit
Save changes and exit