DSE Model 7560 ATS and Mains Controller Operators Manual
057-017 7560 OPERATING MANUAL ISSUE 10.2 10/02/09 AM 33
6.2 AUTOMATIC OPERATION
6.2.1 STARTING
Operation
Detail
If the module is placed in AUTO mode, it will monitor the
incoming mains supply and remote start signal (if
configured).
The LCD display will indicate :
Status
Mains on load
Auto mode
The call to start can come from a number of sources (if configured) :
•
Mains supply failure.
•
Remote start input (either on load, on load demand or in island mode)
Once a call to start is received, the module will initiate its
‘Start Delay’ timer This is used to ensure that the start
event is required and not just a momentary condition.
The 7560 will display:
Status
Start delay
00:05
Auto mode
Once this timer has expired, any available 7510 in auto
mode will be issued with a start signal, and will display:
Please refer to the 7510 operating manual for further
details of the 7510 start sequence.
START DELAY
00:05
The 7560 will display:
Status
Start request
Auto mode