![DSE DSE7560 Скачать руководство пользователя страница 10](http://html1.mh-extra.com/html/dse/dse7560/dse7560_manual_2534921010.webp)
DSE Model 7560 ATS and Mains Controller Operators Manual
10 057-017 7560 OPERATING MANUAL ISSUE 10.2 10/02/09 AM
3.6 OUTPUTS
3.6.1 OUTPUTS A & B (FUEL AND START)
Type
Fuel (A) and Start (B) outputs. Supplied from DC supply terminal 2.
Rating
3A @ 35V
Protection
Protected against over current & over temperature. Built in load dump feature.
3.6.2 CONFIGURABLE OUTPUTS C & D (LOAD SWITCHING)
Type
Fully configurable volts free relays. Output C – Normally Closed, Output D –
Normally Open
Rating
8A @ 230V AC
Protection
Protected against over current & over temperature. Built in load dump feature.
3.6.3 CONFIGURABLE OUTPUTS E, F & G
Type
Fully configurable, supplied from DC supply terminal 2.
Rating
3A @ 35V
Protection
Protected against over current & over temperature. Built in load dump feature.
3.7 COMMUNICATION PORTS
810 port
For connection to the DSE810 interface only
Expansion port
For connection to DSE130, DSE157, DSE545, DSE548 expansion modules only
DSENet
DSE7510 Mk1 controller does not have DSENet expansion capability
CAN Port
Engine CAN Port
Standard implementation of ‘Slow mode’, up to 250K bits/s
Non Isolated.
Internal Termination provided (120
Ω
)
RS485 Serial
Isolated
Data connection 2 wire + common
Half Duplex
Data direction control for Transmit (by s/w protocol)
Max Baud Rate 19200
External termination required (120R)
Max common mode offset 70V (on board protection transorb)
Max distance 1.2km (¾ mile)
3.8 ACCUMULATED INSTRUMENTATION
NOTE : When an accumulated instrumentation value exceeds the maximum number as
listed below, it will reset and begin counting from zero again.
Engine hours run
Maximum 99999 hrs 59 minutes (approximately 11yrs 4months)
Number of starts
1,000,000 (1 million)