DSE Model 7560 ATS and Mains Controller Operators Manual
40 057-017 7560 OPERATING MANUAL ISSUE 10.2 10/02/09 AM
7 PROTECTIONS
The module will indicate that an alarm has occurred in several ways;
The Audible Alarm will sound. This can be silenced by pressing the ‘Mute’ button.
The LCD display will jump from the ‘Status page’ to display the Alarm.
The LCD will then display :
Followed by the appropriate alarm text.
ALARM
Bus failed to open
If no alarms are present, the LCD will display the
following message and will then return to the ‘Status
Display’ page.
No alarm present
The LCD will display multiple alarms E.g. “Bus fail to open”, “Fail to synchronise” and “Mains fail to
close” alarms have been triggered. These will automatically scroll round in the order that they
occurred.
It is also possible to scroll to display the different alarms using the scroll buttons