DSE Model 7560 ATS and Mains Controller Operators Manual
32 057-017 7560 OPERATING MANUAL ISSUE 10.2 10/02/09 AM
The system will remain in this mode until further action is taken.
Pressing the transfer to mains/open bus button
once will synchronise the bus to the mains.
The 7560 will display:
Status
Synchronise bus
Manual mode
Once the bus has synchronised to the mains, the
mains will close and power will be ramped off the
bus (generators). The 7560 will display:
Status
Ramp off bus
10% kW 12% kVAr
Manual mode
Once the bus power / mains power level has been
reached (configured using 75xx software) the
7560 will display:
Status
Continuous paralleling
Manual Mode
The system will remain in this mode until further action is taken.
Operation
Detail
Pressing the transfer to mains/open bus button
again will transfer the remaining load onto the
mains. The 7560 will display:
Status
Ramp off bus
10% kW 12% kVAr
Manual mode
Once the bus loading has reached 0kW the bus
will open and the 7560 will display:
Status
Mains on load
Manual mode
Pressing the red stop button will issue a stop to all
7510s on the system
The LED above the button will illuminate and the
LCD display will briefly indicate:
Status
Mains on load
Stop mode
Any 7510 running in auto mode will then display:
Please refer to the 7510 operating manual for
further details of the 7510 stop sequence
RETURN DELAY
00:50
NOTE:- Pressing the STOP/RESET button
at any time will transfer the load to the
mains and stop the generators.