7.5.2 LIST OF ADJUSTABLE PARAMETERS IN ‘MAIN CONFIGURATION EDITOR’
Front Panel Configuration Editor
(Factory default settings are shown in bold italicised text)
Section Parameter as shown on
Values
Timers
Mains Transient Delay
0 -10s (2s)
Start Delay
0– 60m (5s)
Transfer Delay
0– 10s (0.7s)
Return Delay
0– 60m (30sa0
Low battery Delay
0– 10m (1m)
High battery Delay
0– 10m (1m)`
Mains
Mains Under Voltage Alarm
50V-360V ph-N (184V)
(184V)
(184V)
(184V)
Mains Over Voltage Alarm
50V-360V ph-N (276V)
(276V)
(276V)
(276V)
Mains Under Frequency
0Hz-75Hz (45Hz)
(45Hz)
(45Hz)
(45Hz)
Mains Over Frequency
0Hz-75Hz (55Hz)
(55Hz)
(55Hz)
(55Hz)
System
Plant Battery Under Volt Alarm
0-40V (10V)
(10V)
(10V)
(10V)
Plant Battery Over Alarm
0-40V (30V)
(30V)
(30V)
(30V)
Misc
Language
English, Other
Alternative Frequency
Enable Disable
Disable
Disable
Disable
Alternative Voltage
Enable Disable
Disable
Disable
Disable
AC System
3 phase 4 wire
3 phase 4 wire
3 phase 4 wire
3 phase 4 wire
Single phase 2 Wire
3 phase 3 wire
2 phase 3 wire L1 & L2
3 phase 4 wire ED
2 phase 3 wire L1 & L3
Contrast
l
Date and Time
dd mmm yyyy hh:mm
Auto Scroll Time
0-10s (2s)
(2s)
(2s)
(2s)
Mains CT Primary Rating
5A- 6000A (600A)
(600A)
(600A)
(600A)
Mains CT Secondary Rating
1A, 5A (5A)
(5A)
(5A)
(5A)
Load Ramp Rate
0.1%-100% (2.0%)
2.0%)
2.0%)
2.0%)
(% per sec)
NOTE:- More comprehensive module configuration is possible using the 75xx series PC
configuration software in conjunction with the P810 PC interface. Please contact us for
further details.
NOTE:- Languages are subject to change as the modules are updated. Please contact
us for the list of latest supported languages.