GENERATOR REVERSE POWER, if the module detects a generator reverse power current in
excess of the pre-set trip a shutdown is initiated. The LCD will indicate ‘GEN REVERSE POWER’.
Alarm
Electrical trip
Gen Reverse Power
GENERATOR SHORT CIRCUIT, if the module detects a generator fault current in excess of the
pre-set trip a shutdown is initiated. The LCD will indicate ‘GEN SHORT CIRCUIT’.
Alarm
Electrical trip
Gen Short Circuit
LOSS OF EXCITATION, the module will monitor the KVAr present on the generator. Should this
exceed a pre-set amount of negative Var this indicates a possible loss of excitation on the
alternator. The following alarm will then be generated.
Alarm
Electrical trip
Loss of Excitation
NEGATIVE PHASE SEQUENCE, if the module detects an imbalance in the load current of each
phase above a pre-set level, then the following warning will occur.
Alarm
Electrical Trip
Negative phase Sequence
kW OVERLOAD ALARM
The kW level provided by the set is above the level of the kW Overload Electrical Trip.
Alarm
Electrical Trip
kW Overload Alarm
ENGINE INLET TEMPERATURE
The engine inlet temperature (electronic engines only) is above the level of the Engine Inlet
Temperature Electrical Trip alarm.
Alarm
Electrical Trip
Engine Inlet Temperature