GENERATOR HIGH FREQUENCY, if the module detects a generator output frequency in excess of
the pre-set pre-alarm, a warning is initiated. Alarm Warning High frequency will be displayed, it is an
immediate warning.
Alarm
Warning
Gen high frequency
GENERATOR LOW FREQUENCY, if the module detects a generator output frequency below the
pre-set pre-alarm after the Safety On timer has expired, a warning is initiated. Alarm Warning Low
Frequency will be displayed
Alarm
Warning
Gen low frequency
GENERATOR HIGH VOLTAGE, if the module detects a generator output voltage in excess of the
pre-set pre-alarm, a warning is initiated. Alarm Warning High voltage will be displayed, it is an
immediate warning.
Alarm
Warning
Gen high voltage
GENERATOR LOW VOLTAGE, if the module detects a generator output voltage below the pre-set
pre-alarm after the Safety On timer has expired, a warning is initiated. Alarm Warning Low Voltage
will be displayed.
Alarm
Warning
Gen low voltage