MSC TOO FEW SETS, if the module detects fewer modules on the MSC link than the minimum
number configured in the unit the MSC Too few sets alarm will be triggered. This may indicate a
break in the MSC connection between the sets.
Alarm
MSC Too Few Sets
CAN ECU ERROR, If the module is configured for CAN Bus instruments and receives an
“error” message from the engine control unit, ‘Can ECU error” is shown on the module’s
display and a warning alarm is generated.
Example
Alarm
The display will alternate
between the text display
and the manufacturers
error codes
Alarm
Can ECU error
Exhaust high
temperature
Can ECU error
SPNnnnnnnn
FMInnnnnnn
kW OVERLOAD ALARM
The kW level provided by the set is above the level of the kW Overload pre alarm.
Alarm
kW Overload Alarm
ENGINE INLET TEMPERATURE
The engine inlet temperature (electronic engines only) is above the level of the Engine Inlet
Temperature alarm.
Alarm
Engine Inlet Temperature
AVR MAXIMUM TRIM LIMIT
The AVR output is beng controlled to its maximum limit (100%). This can indicate a problem with the
setup or control of the AVR.
Alarm
AVR Maximum Trim Limit