5.4.3 LIST OF ADJUSTABLE PARAMETERS IN ‘MAIN CONFIGURATION EDITOR’
(Factory default settings are shown in bold italicised text)
Section
Parameter as shown on display
Values
Input settings
Oil Pressure Pre Alarm
0bar - 4bar (1.17bar)
Oil Pressure Shutdown
0bar - 4bar (1.03bar)
High Coolant Temp Pre Alarm
80
°
C - 140
°
C (115
°°°°
C)
High Coolant Temp Shutdown
80
°
C - 140
°
C (120
°°°°
C)
Timers
Gen Transient Delay
0 -10s (0s)
Start Delay
0 - 60m (5s)
Pre Heat Time
0 - 60m (0s)
Crank Time
0 - 60s (10s)
Crank Rest Time
0 - 60s (10s)
Safety On Delay
0 - 30s (10s)
Over speed Overshoot Delay
0 - 10s (0s)
Warm Up Time
0 - 60m (0s)
Return Delay
0 - 60m (30s)
Cooling Run Time
0 - 60m (1m)
Fail To Stop Delay
0 - 30s (30s)
Low Battery Delay
0- 10m (1m)
High Battery Delay
0 -10m (1m)
Gen Reverse Power Delay
0- 30s (2s)
Generator
Generator Under Voltage Shutdown
50V-360V ph-N (184V)
Generator Under Voltage Pre Alarm
50V-360V ph-N (196V)
Generator Nominal Voltage
52V-330V(230V)
Generator Over Voltage Pre Alarm
50V-360V ph-N (265V)
Generator Over Voltage Shutdown
50V-360V ph-N (277V)
Generator Under Frequency Shutdown
0Hz - 75Hz (40Hz)
Generator Under Frequency Pre Alarm
0Hz - 75Hz (42Hz)
Generator Nominal Frequency
0Hz - 74Hz (50Hz)
Generator Over Frequency Pre Alarm
0Hz - 75Hz (55Hz)
Generator Over Frequency Shutdown
0Hz - 75Hz (57Hz)
Generator Over Current Trip
100% - 200% full load rating
(100%)
Generator Short Circuit Trip
50% - 300% full load rating (200%)
Generator Reverse Power Trip
0% - 200% full load rating (35kW)
Earth Fault Trip
1% - 100% full load rating (10%)
Engine
Engine Under speed Shutdown
0RPM - 6000RPM (disabled)
Engine Under speed Pre Alarm
0RPM - 6000RPM (disabled)
Engine Over speed Pre Alarm
0RPM - 6000RPM (disabled)
Engine Over speed Shutdown
0RPM - 6000RPM (disabled)
Over speed Overshoot
0% - 10% (0%)
Plant Battery Under Volt Alarm
0V - 40V (10V)
Plant Battery Over Volt Alarm
0V - 40V (30V)
Charge Alternator Failure Alarm
0V - 40V (6V)
Display
Language
ENGLISH, OTHERS
AC System
Alternative Frequency
Enable, Disable
Alternative Voltage
Enable, Disable
AC System
3 Ph 4 wire, 1 Ph 2 wire,
3 ph 3 wire, 2 ph 3 wire L1 & L2
3 ph 4 wire EDISON DELTA
2 ph 3 wire L1 & L3
Generator Full Load Current
0A - 8000A
(500A)
(500A)
(500A)
(500A)
Droop
Enable, Disable
Droop %
0
0
0
0 %
%
%
% - 5%
Electronic engines only
when Droop is enabled
Display
Contrast
|
Clock
Date and Time
dd mmm yyyy hh:mm:ss
Misc.
Run Priority
1-16 (1)
Auto Scroll Time
0 - 10s (2.0s)
CT
Generator CT Primary Rating
0A - 8000A (600A)
Power Cycle After Exit
Generator CT Secondary Rating
1A, 5A
Power Cycle After Exit
Power
Full kW Rating
0MW-20MW (245kW)
Power Cycle After Exit
Full kVAr Rating
0MVA-20MVAr (258kVAr)
Power Cycle After Exit
Load Ramp Rate
0%-100% (3.0%)
Load Level For More Sets
0%-100% (80%)
Load Level For Less sets.
0%-100% (70%)
Load Parallel Power
0%-100% (172kW)
Load Power Factor
0%-100% (1.0pfF OkVAr 0%)
Ramp With P123 Present
Enable Disable
Reactive Load Ctl Mode
None, VAr Share, VAr Fixed Export
Insufficient Capacity Delay
0 – 30m (1s)
Insufficient Capacity Action
None, Shutdown, Electrical Trip,
Latched Warning,
Unlatched Warning
AVR Trim limit Delay
Mm:ss (
0s
0s
0s
0s)
AVR Trim limit action
None
None
None
None/Unlatched Warning/Latched
Warning/Electrical
trip/Shutdown
NOTE:- More comprehensive module configuration is possible using the 5xxx series PC configuration
software in conjunction with the P810 PC interface. Please contact us for further details.
NOTE:- Languages are subject to change as the modules are updated. Please contact us for the list of latest
supported languages.