057-015 5510 OPERATING MANUAL ISSUE 11 07/07/09 AM 15
4.1 WARNINGS
Warnings are non-critical alarm conditions and do not affect the operation of the generator system.
They draw the operators’ attention to an undesirable condition.
In the event of an alarm the LCD will jump to the alarms page and scroll through all active warnings
and shutdowns.
BATTERY CHARGE FAILURE, will be displayed if the module does not detect a voltage from the
warning light terminal on the auxiliary charge alternator.
Alarm
Warning
Charge alt failure
BATTERY LOW VOLTAGE will be displayed if the module detects that the plant DC supply has
fallen below the low volts setting level. The Battery Low Voltage alarm is delayed by the Low DC
Volts Delay timer.
Alarm
Warning
Low battery voltage
BATTERY HIGH VOLTAGE will be displayed if the module detects that the plant DC supply has
risen above the high volts setting level. The Battery High Voltage alarm is delayed by the High DC
Volts Delay timer.
Alarm
Warning
High battery voltage
FAIL TO STOP, will be displayed if the module detects the engine is still running when the ‘Fail to
stop timer’ expires.
Alarm
Fail to stop
NOTE:- ‘Fail to Stop’ could indicate a faulty oil pressure sender - If engine is at rest
check oil sender wiring and configuration.