Specification
Page 23 of 188
057-254 ISSUE: 2
2.9 COMMUNICATION PORTS
NOTE: All communication ports can be used at the same time.
Description
Specification
USB Slave Port
Type B USB 2.0
For connection to PC running DSE Configuration Suite
Max distance 6 m (20 feet)
USB Host Port
Type A USB 2.0
Capability to add a maximum of 16 GB USB storage device for data
recording only
RS232 Serial Port
Non – isolated
Max Baud rate 115 k baud subject to configuration
TX, RX, RTS, CTS, DSR, DTR, DCD
Male 9 way D type connector
Max distance 15 m (50 feet)
2 x RS485 Serial Ports
Isolated
Data connection 2 wire + common
Half Duplex
Data direction control for Transmit (by s/w protocol)
Max Baud Rate 115 k baud subject to configuration
External termination required (120
Ω
)
Max common mode offset 70 V (on board protection transorb)
Max distance 1.2 km (¾ mile)
Ethernet
Auto detecting 10/100 Mbit Ethernet port.
MSC (Multi Set
Communication) and
CAN Port
NOTE: For additional length, the DSE124 CAN & MSC Extender
is available. For more information, refer to DSE Publication: 057-116
DSE124 Operator Manual
Standard implementation of ‘Slow mode’, up to 250K bits/s
Data connection 2 wire + common
Isolated
External termination required (120
Ω
)
Max common mode offset 70 V (on board protection transorb)
Max distance 250 M using Belden 9841 Cable or equivalent
ECU Port
NOTE: For additional length, the DSE124 CAN & MSC Extender
is available. For more information, refer to DSE Publication: 057-116
DSE124 Operator Manual
Engine CAN Port
Standard implementation of ‘Slow mode’, up to 250 Kb/s
Non-Isolated.
Internal Termination enabled by software configuration provided (120
Ω
)
Max distance 40 m (133 feet)
DSENet
®
(Expansion Comms) Port
Non-isolated
Data connection 2 wire + common
Half Duplex
Data direction control for Transmit (by s/w protocol)
Baud Rate of 115 k baud
Internal termination fitted (120
Ω
)
Max common mode offset ±5 V
Max distance 1.2 km (¾ mile)
Содержание 8610 MKII
Страница 63: ...Installation Page 63 of 188 057 254 ISSUE 2 3 4 2 SINGLE PHASE L1 N 2 WIRE WITHOUT EARTH FAULT...
Страница 65: ...Installation Page 65 of 188 057 254 ISSUE 2 3 4 4 SINGLE PHASE L1 L2 3 WIRE WITHOUT EARTH FAULT...
Страница 67: ...Installation Page 67 of 188 057 254 ISSUE 2 3 4 6 SINGLE PHASE L1 L3 3 WIRE WITHOUT EARTH FAULT...
Страница 69: ...Installation Page 69 of 188 057 254 ISSUE 2 3 4 8 2 PHASE L1 L2 3 WIRE WITHOUT EARTH FAULT...
Страница 71: ...Installation Page 71 of 188 057 254 ISSUE 2 3 4 10 2 PHASE L1 L3 3 WIRE WITHOUT EARTH FAULT...
Страница 72: ...Installation 057 254 ISSUE 2 Page 72 of 188 3 4 11 3 PHASE 3 WIRE DETLA WITHOUT EARTH FAULT...
Страница 82: ...Installation 057 254 ISSUE 2 Page 82 of 188 3 5 7 SINGLE GENERATOR EXPORTING BASE LOADING POWER...
Страница 187: ...This Page is Intentionally Blank...