Fault Finding
Page 181 of 188
057-254 ISSUE: 2
9 FAULT FINDING
NOTE: The below fault finding is provided as a guide check-list only. As the module can
be configured to provide a wide range of different features, always refer to the source of the
module configuration if in doubt.
9.1 STARTING
Symptom
Possible Remedy
Unit is inoperative
Read/Write configuration
does not operate
Check the battery and wiring to the unit. Check the DC supply. Check
the DC fuse.
Unit shuts down
Check DC supply voltage is not above 35 Volts or below 9 Volts
Check the operating temperature is not above 70°C. Check the DC
fuse.
Fail to Start is activated after
pre-set number of attempts to
start
Check wiring of fuel solenoid. Check fuel. Check battery supply.
Check battery supply is present on the Fuel output of the module.
Check the speed-sensing signal is present on the module’s inputs.
Refer to engine manual.
Continuous starting of
generator when in the
Auto Mode
Check that there is no signal present on the “Remote Start” input.
Check configured polarity is correct.
Generator fails to start on
receipt of Remote Start
signal.
Check Start Delay timer has timed out.
Check signal is on “Remote Start” input. Confirm correct
configuration of input is configured to be used as “Remote Start”.
Check that the oil pressure switch or sensor is indicating low oil
pressure to the controller. Depending upon configuration, the set
does not start if oil pressure is not low.
Pre-heat inoperative
Check wiring to engine heater plugs. Check battery supply. Check
battery supply is present on the Pre-heat output of module. Check
pre-heat configuration is correct.
Starter motor inoperative
Check wiring to starter solenoid. Check battery supply. Check battery
supply is present on the Starter output of module. Ensure oil
pressure switch or sensor is indicating the “low oil pressure” state to
the controller.
9.2 LOADING
Symptom
Possible Remedy
Engine runs but generator
does not take load
Check Warm up timer has timed out.
Ensure generator load inhibit signal is not present on the module
inputs.
Check connections to the switching device.
Note that the set does not take load in Manual Mode
unless
there is an active load signal.
Incorrect reading on Engine
gauges
Fail to stop alarm when
engine is at rest
Check engine is operating correctly.
Check that sensor is compatible with the module and that the module
configuration is suited to the sensor.
Содержание 8610 MKII
Страница 63: ...Installation Page 63 of 188 057 254 ISSUE 2 3 4 2 SINGLE PHASE L1 N 2 WIRE WITHOUT EARTH FAULT...
Страница 65: ...Installation Page 65 of 188 057 254 ISSUE 2 3 4 4 SINGLE PHASE L1 L2 3 WIRE WITHOUT EARTH FAULT...
Страница 67: ...Installation Page 67 of 188 057 254 ISSUE 2 3 4 6 SINGLE PHASE L1 L3 3 WIRE WITHOUT EARTH FAULT...
Страница 69: ...Installation Page 69 of 188 057 254 ISSUE 2 3 4 8 2 PHASE L1 L2 3 WIRE WITHOUT EARTH FAULT...
Страница 71: ...Installation Page 71 of 188 057 254 ISSUE 2 3 4 10 2 PHASE L1 L3 3 WIRE WITHOUT EARTH FAULT...
Страница 72: ...Installation 057 254 ISSUE 2 Page 72 of 188 3 4 11 3 PHASE 3 WIRE DETLA WITHOUT EARTH FAULT...
Страница 82: ...Installation 057 254 ISSUE 2 Page 82 of 188 3 5 7 SINGLE GENERATOR EXPORTING BASE LOADING POWER...
Страница 187: ...This Page is Intentionally Blank...
Страница 188: ...This Page is Intentionally Blank...