Operation
057-254 ISSUE: 2
Page 116 of 188
5.4
AUTOMATIC MODE
NOTE: If a digital input configured to external Panel Pock is active, changing module
modes is not possible. Viewing the instruments and event logs is NOT affected by Panel Lock.
Auto Mode is activated by pressing the Auto Mode
button.
The LED above the Auto Mode
button illuminates to indicate Auto Mode
operations.
Auto Mode
allows the generator to operate fully automatically, starting and stopping as required
with no user intervention.
5.4.1 WAITING IN AUTO MODE
If a starting request is made, the starting sequence begins.
Starting requests can be from the following sources:
•
Activation of the inbuilt exercise scheduler.
•
Activation of an auxiliary input that has been configured to Remote Start On Load, Remote
Start On Load Demand or Remote Start Off Load.
•
Request from a DSExx60 or from another DSExx10 controller over the MSC link.
•
Instruction from external remote telemetry devices using the RS232, RS485 or Ethernet
interface.
Содержание 8610 MKII
Страница 63: ...Installation Page 63 of 188 057 254 ISSUE 2 3 4 2 SINGLE PHASE L1 N 2 WIRE WITHOUT EARTH FAULT...
Страница 65: ...Installation Page 65 of 188 057 254 ISSUE 2 3 4 4 SINGLE PHASE L1 L2 3 WIRE WITHOUT EARTH FAULT...
Страница 67: ...Installation Page 67 of 188 057 254 ISSUE 2 3 4 6 SINGLE PHASE L1 L3 3 WIRE WITHOUT EARTH FAULT...
Страница 69: ...Installation Page 69 of 188 057 254 ISSUE 2 3 4 8 2 PHASE L1 L2 3 WIRE WITHOUT EARTH FAULT...
Страница 71: ...Installation Page 71 of 188 057 254 ISSUE 2 3 4 10 2 PHASE L1 L3 3 WIRE WITHOUT EARTH FAULT...
Страница 72: ...Installation 057 254 ISSUE 2 Page 72 of 188 3 4 11 3 PHASE 3 WIRE DETLA WITHOUT EARTH FAULT...
Страница 82: ...Installation 057 254 ISSUE 2 Page 82 of 188 3 5 7 SINGLE GENERATOR EXPORTING BASE LOADING POWER...
Страница 187: ...This Page is Intentionally Blank...
Страница 188: ...This Page is Intentionally Blank...