Operation
Page 115 of 188
057-254 ISSUE: 2
5.3.2 ENGINE RUNNING
NOTE: The load transfer signal remains inactive until the generator is available. This
prevents excessive wear on the engine and alternator.
In Manual Mode
, the generator does not synchronise and close it’s load switch unless a ‘loading
request’ is made.
A loading request can come from a number of sources.
•
Press the Close Generator
button.
•
Activation of the inbuilt exercise scheduler if configured for ‘on load’ runs.
•
Activation of an auxiliary input that has been configured to Remote Start On Load or Remote
Start On Load Demand
•
Request from a DSExx60 or from another DSExx10 controller over the MSC link.
•
Instruction from external remote telemetry devices using the RS232, RS485 or Ethernet
interface.
Once the generator has been instructed to synchronise and placed on load, it is not automatically
removed. To instruct the generator to ramp its load off and open its load switch either:
•
Press the Open Generator
•
Press the Auto Mode
button to return to automatic mode. The set observes all
Auto Mode
start requests and stopping timers before beginning the Auto Mode Stopping
Sequence.
•
Press the Stop/Reset Mode
button to remove load and stop the generator.
•
Activation of an auxiliary input that has been configured to Generator Load Inhibit (no ramping
occurs).
5.3.3 STOPPING SEQUENCE
In Manual Mode
the set continues to run until either:
•
The Stop/Reset Mode
button is pressed – The delayed load outputs are de-activated
immediately and the set immediately stops.
•
The Auto Mode
button is pressed. The set observes all Auto Mode
start requests
and stopping timers before beginning the Auto Mode Stopping Sequence.
Содержание 8610 MKII
Страница 63: ...Installation Page 63 of 188 057 254 ISSUE 2 3 4 2 SINGLE PHASE L1 N 2 WIRE WITHOUT EARTH FAULT...
Страница 65: ...Installation Page 65 of 188 057 254 ISSUE 2 3 4 4 SINGLE PHASE L1 L2 3 WIRE WITHOUT EARTH FAULT...
Страница 67: ...Installation Page 67 of 188 057 254 ISSUE 2 3 4 6 SINGLE PHASE L1 L3 3 WIRE WITHOUT EARTH FAULT...
Страница 69: ...Installation Page 69 of 188 057 254 ISSUE 2 3 4 8 2 PHASE L1 L2 3 WIRE WITHOUT EARTH FAULT...
Страница 71: ...Installation Page 71 of 188 057 254 ISSUE 2 3 4 10 2 PHASE L1 L3 3 WIRE WITHOUT EARTH FAULT...
Страница 72: ...Installation 057 254 ISSUE 2 Page 72 of 188 3 4 11 3 PHASE 3 WIRE DETLA WITHOUT EARTH FAULT...
Страница 82: ...Installation 057 254 ISSUE 2 Page 82 of 188 3 5 7 SINGLE GENERATOR EXPORTING BASE LOADING POWER...
Страница 187: ...This Page is Intentionally Blank...
Страница 188: ...This Page is Intentionally Blank...