Description of Controls
Page 101 of 188
057-254 ISSUE: 2
4.2.7.1
PROTECTIONS DISABLED
NOTE: For further details on Protections Disabled, see section entitled Protections
elsewhere in this manual.
Configuration is possible to prevent Shutdown and Electrical Trip alarms from stopping the generator.
Under such conditions the operator is informed the events were blocked.
Example:
1
Event Log
Oil Pressure Low
Shutdown Blocked
4.2.7.2
RESET ELECTRICAL TRIP
NOTE: For further details on Reset Electrical Trip, see section entitled Protections
elsewhere in this manual.
Configuration is possible to enable the operator to reset Electrical Trip alarm a configurable number of
times before the generator has stopped. This is to allow the generator to go back on load without
having to perform a cooling run first. Under such conditions the operator is informed the events were
overridden.
Example:
2
Event Log
Gen Over Current
Running Electrical Trip
Содержание 8610 MKII
Страница 63: ...Installation Page 63 of 188 057 254 ISSUE 2 3 4 2 SINGLE PHASE L1 N 2 WIRE WITHOUT EARTH FAULT...
Страница 65: ...Installation Page 65 of 188 057 254 ISSUE 2 3 4 4 SINGLE PHASE L1 L2 3 WIRE WITHOUT EARTH FAULT...
Страница 67: ...Installation Page 67 of 188 057 254 ISSUE 2 3 4 6 SINGLE PHASE L1 L3 3 WIRE WITHOUT EARTH FAULT...
Страница 69: ...Installation Page 69 of 188 057 254 ISSUE 2 3 4 8 2 PHASE L1 L2 3 WIRE WITHOUT EARTH FAULT...
Страница 71: ...Installation Page 71 of 188 057 254 ISSUE 2 3 4 10 2 PHASE L1 L3 3 WIRE WITHOUT EARTH FAULT...
Страница 72: ...Installation 057 254 ISSUE 2 Page 72 of 188 3 4 11 3 PHASE 3 WIRE DETLA WITHOUT EARTH FAULT...
Страница 82: ...Installation 057 254 ISSUE 2 Page 82 of 188 3 5 7 SINGLE GENERATOR EXPORTING BASE LOADING POWER...
Страница 187: ...This Page is Intentionally Blank...
Страница 188: ...This Page is Intentionally Blank...