DSC PowerSeries PC1404 V1.1 Скачать руководство пользователя страница 8

1 Introduction

1

1 Introduction

This manual provides installation and programming information for the PC1404 four-zone panel security system. 

1.1 Compatibility Requirements

The PC1404 product is the central component of the four-zone security system. Interaction with associated system devices is hardwired, 

which follows DSC keybus standards. Communications with the central station may be achieved by a hardwired phone line. DLS may 

also be remotely connected to the panel via phone line or locally connected via the PC-Link header. Shown below are the supported and 
unsupported modules for the PC1404. 

1.2 Product Specifications
Control and Indicating Equipment Specifications
Features 

• Supports zone doubling — supervised and distinguishable

• NC/Single/Double EOL support

Note: 

All necessary information required to meet UL listing requirements is included in this document. 

7DEOH6XSSRUWHG0RGXOHV

Module

Current Draw, mA

Software Versions

PC1404RKZ Keypad*

120

1.0

PK5500/PK5501/PK5508/PK5516 Keypads* 

125

1.0, 1.1, 1.2, 1.3

LCD5511 Fixed Message LCD Keypad*

85

1.0

LED5511 8-Zone LED Keypad* 

100

1.0

PC1555RKZ 8-Zone LED Keypad*

85

2.0

PC5200 Power Supply*

20

2.0

PC5204 Power Supply with 4 PGMs*

20

2.0

PC5208 Low Current PGM Module*

20

1.0

PC5601 LED Status Module

30

1.0

TL300 T-Link TL300 IP Alarm Communicator*

360

1.2-1.5

GS3060 GPRS Universal Cellular Alarm Communicator*

120 3.1, 

3.2

3G3070 HSPA (3G) Universal Cellular Alarm Communicator*

120

3.5

GS3105/3125-K & BA Wireless Alarm Communicator

250 (excluding outputs)

3.0

*UL/ULC-listed devices.

Note: 

For UL/ULC-listed installations, use only UL/ULC-listed devices. 

Note: 

For SIA CP-01: 2010 compliant installations, the minimum required components are: PC1404 Control Panel and PC1404RKZ 

keypad. Optional components that can be used with the system are: PK55XX series keypad. These keypads can only be used for SIA 

CP-01: 2010 Compliant installations if the emergency keys are not enabled.

7DEOH8QVXSSRUWHG0RGXOHV

7DEOH&RPSDWLEOH6PRNH'HWHFWRU0RGHOV

Module

4-Wire Smoke Detectors

2-Wire Smoke Detectors

PC5100 2-wire interface

PC5964 Large Audio Station

FSA-410x

FSA-210x

RFK55XX Keypad

PC5401 RS232 Module

FSA-410xT

FSA-210xT

RF5132-433 Wireless Receiver

PC5400 P DVACS

FSA-410xS

FSA-210xS

RF5108-433 Wireless Receiver

Escort 5580 Telephone 

Interface

FSA-410xST

FSA-210xST

PC5108 Zone Expander

TL260 Series Communicators

FSA-410xLST

FSA-210xLST

PC5320 Zone Expander

GS2060 Series Wireless

Alarm Communicator

FSA-410xR

FSA-210xR

PC5950 Audio Module

TL250 Communicator

FSA-410xRT

FSA-210xRT

PC5904 Large Audio Station

TL150 Communicator

FSA-410xRS

FSA-210xRS

PC5921 Audio Station

IT100 Integration Module

FSA-410xRST

FSA-210xRST

PC5961, PC5962 Small Audio 

Station

IT120 Integration Module

FSA-410xLRST

FSA-210xLRST

PTK5507 Touchscreen keypad

Note: 

For model numbers above, x = A (ULC); x = B (UL); x = C (CE)

Содержание PowerSeries PC1404 V1.1

Страница 1: ...on Guide WARNING This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer The entire manual should be c...

Страница 2: ...damage For direct plug in versions use the transformer supplied with the device WARNING THIS EQUIPMENT WHEN POWERED VIA DIRECT PLUG IN TRANSFORMER HAS NO MAINS ON OFF SWITCH THE PLUG OF THE DIRECT PL...

Страница 3: ...Smoke detectors should always be installed in USA in accordance with Chapter 29 of NFPA 72 the National Fire Alarm Code 29 5 1 1 Where required by other governing laws codes or standards for a specifi...

Страница 4: ...ructions They cannot discriminate between intruders and intended occupants Motion detectors do not provide volumetric area protection They have multiple beams of detection and motion can only be detec...

Страница 5: ...Zones 7 3 Keypad Commands 10 3 1 Arming and Disarming 10 3 2 Auto Bypass Stay Arming 10 3 3 Automatic Arming 10 3 4 Night Arming 10 3 5 Commands 10 4 Programming 16 4 1 Installer Programming 16 4 2 Pr...

Страница 6: ...R Minimum System Requirements 1 PC1404 Panel 1 Local annunciation devices Local annunciation devices may be any combination of these keypads PK5500 PK5501 PK5508 PK5516 PC1404RKZ LCD5511 LED5511Z PC15...

Страница 7: ...ersons only service person is defined as a person having the appropriate technical training and experience necessary to be aware of hazards to which that person may be exposed in performing a task and...

Страница 8: ...GS3060 GPRS Universal Cellular Alarm Communicator 120 3 1 3 2 3G3070 HSPA 3G Universal Cellular Alarm Communicator 120 3 5 GS3105 3125 K BA Wireless Alarm Communicator 250 excluding outputs 3 0 UL ULC...

Страница 9: ...protection fixed at 9 6V Aux Voltage 11 1 12 5VDC Current 550mA Max Note Aux and PGM outputs share the 550mA load Keybus Terminals Clock yellow Data green Memory 32Kbit serial CMOS EEPROM with write...

Страница 10: ...Please verify that all modules appear on the system according to the instructions in Section 2 6 Keypad Assignment Step 9 Programming the System Sections 4 5 Section 4 Programming explains how to pro...

Страница 11: ...and metallic plating requirements of 47 C F R Part 68 SubPart F For proper operation no other telephone equipment should be connected between the control panel and the tele phone company facilities D...

Страница 12: ...key twice to exit programming d After assigning all keypads perform a supervisory reset by entering 8 Installer Code 902 The panel will reset supervision and re enroll modules on the system How to Pro...

Страница 13: ...To enable zone doubling Section 13 Option 7 must be ON All zones must be wired according to the following diagram Only Normally Closed devices can be used with zone doubling Note All resistors are 5 t...

Страница 14: ...d of line supervision connect the zone according to one of the configurations outlined in Section 2 9 Zone Wiring End of line resistors must be placed on the device end of the loop not at the keypad N...

Страница 15: ...RED positive terminal and the black wire to the BLK negative terminal When using end of line supervision connect the zone according to one of the configurations outlined in your system s Installation...

Страница 16: ...off press 5 5 To control whether the LED indicates AC present or absent press 6 6 When complete press to exit Backlighting Intensity Adjustment The keypad has 5 backlighting intensity settings To adj...

Страница 17: ...ad Function Programming in PC1404 Pro gramming Descriptions 3 3 Automatic Arming The system can be programmed to arm at the same time each day Upon entry of this section enter 4 digits for the 24 Hour...

Страница 18: ...stem is armed in the Stay mode by a arming and not exiting through a delay zone during the exit delay or b pressing a function key programmed for Stay Arm or Arming Without Entry Delay 9 the zones pro...

Страница 19: ...fter the AC fail transmission delay if Trouble 2 is NOT present 2 AC Failure There is no audible annunciation on AC power failure unless trouble beeps on AC failure are enabled in Section 018 Option 8...

Страница 20: ...still squawk 8 One Time Use Code When the one time use code is entered on the system the user of the code will be able to arm the panel with the code as many times as they want They will also be able...

Страница 21: ...te using the following format HH MM MM DD YY Program the time using military standard e g 8 00 pm 20 00 hours Valid entries for the Hour are 00 23 Valid entries for the Minute are 00 59 2 Auto Arm Con...

Страница 22: ...n Stay Mode or Armed in Away Mode for this closing type 0 Quick Exit When armed press 0 to activate Quick Exit Quick Exit allows the user 2 minutes to exit the premises through any delay zone with out...

Страница 23: ...one digit in each box in the programming section in order for the change to be valid 4 2 Programming Decimal Data A set number of programming boxes are allotted for each section requiring decimal dat...

Страница 24: ...ED and Fixed Message LCD Keypads Any programming section can be viewed from an LED keypad When a programming section is entered the keypad will immediately display the first digit of information progr...

Страница 25: ...330 Tamper Rep Codes 26 334 Tamper Restore Rep Codes 26 338 Misc Tamper Rep Codes 26 339 340 Closing Arming Rep Codes 26 341 Misc Closing Arming Rep Codes 26 342 343 Opening Disarming Rep Codes 26 344...

Страница 26: ...7 1 Reactivate Stay Away Zones 26 33 Future Use This function key must not be used in CP 01 listed systems Key 1 Key 2 Key 3 Key 4 Key 5 Keypad Defaults BBB BBB BBB BBB BBB 00 Null Zone Not Used 14 24...

Страница 27: ...____I 123456 I_______I_______I_______I_______I_______I_______I AAAA00 I_______I_______I_______I_______I_______I_______ Programmable Output Options 00 Null PGM Not Used 01 Burglary and Fire Output 02 N...

Страница 28: ...e Doubling Enabled Zone Doubling Disabled 8 Temporal Three Fire Signal Enabled Standard Pulsed Fire Signal Note When Option 7 is ON the configuration of Options 1 and 2 should be ignored Opt Def ON OF...

Страница 29: ...Enabled ON for SIA CP 01 Exit Delay Restart Disabled 8 System AC Failure Trouble Beeps Enabled System AC Failure Trouble Beeps Disabled Default 00 I_______I_______I Keypad Address 1 Zone Valid entries...

Страница 30: ...lsed No No No No No 00 Null Zone 01 Delay 1 02 Delay 2 03 Instant 04 Interior 05 Interior Stay Away 06 Delay Stay Away 07 Delay 24 hr Fire Hardwired 08 Stand 24 hr Fire Hardwired 09 24 hr Supervisory...

Страница 31: ...20 24 hr Freeze 21 24 hr Latching Tamper 22 Momentary Keyswitch Arm 23 Maintained Keyswitch Hardwired 24 Not Used 25 Interior Delay 26 24 hr Non Alarm 27 30 Not Used 31 Day Zone 32 Instant Stay Away 3...

Страница 32: ...__I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I____I 302 Second Telephone Number 32 Digits I__D___I_____I_____I_...

Страница 33: ...__ ___ ___ ___ ___ ___ ___ General System Tamper ___ ___ General System Tamper Restore ___ ___ Keypad Lockout Section 339 Code 1 Code 2 Code 3 Code 4 Code 5 Code 6 Code 7 Code 8 ___ ___ ___ ___ ___ __...

Страница 34: ...___ AC Failure Trouble Restore ___ ___ General System Trouble Restore ___ ___ Bell Circuit Trouble Restore ___ ___ General System Supervisory Restore ___ ___ Fire Trouble Restore ___ ___ System Reset...

Страница 35: ...I_______I______I_______I Swinger Shutdown Tampers and Rest 001 014 Transmissions 001 006 for CP 01 000 disabled 003 I_______I______I_______I Swinger Shutdown Maint and Rest 001 014 Transmissions 001...

Страница 36: ...ting Cancel Disabled 5 For Future Use For Future Use 6 AC Failure Communications Delay is in Hours AC Failure Communications Delay is in Minutes 7 Number of Dialing Attempts for Residential Dial is 1...

Страница 37: ...__ ___ ___ ___ ___ ___ ___ ___ PC5208 503 PGM 3 ___ ___ ___ ___ ___ ___ ___ ___ 504 PGM 4 ___ ___ ___ ___ ___ ___ ___ ___ 505 PGM 5 ___ ___ ___ ___ ___ ___ ___ ___ 506 PGM 6 ___ ___ ___ ___ ___ ___ __...

Страница 38: ...bled Disabled Disabled 09 System Trouble Attribute 1 2 3 4 5 6 7 8 ON OFF Burglary Event Fire Event Panic Event Medical Event Supervisory Event Priority Event Duress Event Output Follows Timer Disable...

Страница 39: ...ode 35 Code 36 Code 37 Code 38 Code 39 Code 40 ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ Code 33 Code 34 Code 35 Code 36 Code 37 Code 38 Code 39 Code 40 ___ ___ ___ ___ ___ ___ _...

Страница 40: ...5 Programming Worksheets 33 991 Installer Lockout Disable 999 Restore Panel Factory Defaults Enter 991 Installer s Code 991 Enter 999 Installer s Code 999...

Страница 41: ...red Press 1 to determine specific trouble 1 Low Battery Main panel battery less than 11 1 VDC Note This trouble condition will not clear until the battery voltage is 12 5 VDC min under load Note If ba...

Страница 42: ...across AC terminals is 16 18VAC Replace transformer if required Trouble 2 AC Failure AC Failure No AC at panel AC input terminals Verify voltage measured across AC terminals is 16 18VAC Replace transf...

Страница 43: ...e trouble condi tion clears A short circuit is present on one or more zones with double end of line resistors enabled Remove the wire leads from Z and COM terminals and measure the resistance of the w...

Страница 44: ...nt when the system is disarmed after an alarm but before the expiry of the alarm cancellation timer A R E 4 A6 UUU OC UU 329 F Key Alarm Rest Keypad fire alarm alarm and restore rep codes sent togethe...

Страница 45: ...delinquency has expired without zone activity or without system being armed MA R E 6 54 000 CD 00 347 Installer Lead In Installer s mode has been entered MA R E 6 27 000 LB 00 347 Installer Lead Out...

Страница 46: ...upervisory Buzzer UA ZZ UH ZZ E 1 4A ZZZ E 1 4A ZZZ 24 Hr Burg BA ZZ BH ZZ E 1 3A ZZZ E 1 3A ZZZ 24 Hr Gas GA ZZ GH ZZ E 1 51 ZZZ E 1 51 ZZZ 24 Hr Heat KA ZZ KH ZZ E 1 58 ZZZ E 1 58 ZZZ 24 Hr Medical...

Страница 47: ...the account number substitute the HEX digit A for the 0 All reporting codes must be two digits If the digit 0 is in the reporting code substitute the HEX digit A for the 0 To prevent the panel from re...

Страница 48: ...vate line format allows the communication of zone alarms directly to a user over a telephone line When an event occurs that the panel is programmed to commu nicate the panel seizes the line and dials...

Страница 49: ...ements adopted by the ACTA On the side of this equipment is a label that contains among other information a product identifier If requested this number must be provided to the Telephone Company Produc...

Страница 50: ...tions Delay Abort Window shall not exceed 60s Range 20 45 sec Default 30 sees Required programmable Abort Annunciation 382 Option 3 ON Enables the Communication Cancelled message display on keypad Ann...

Страница 51: ...e minimum Bell Time out is 4 minutes Refer to section 005 Note For ULC Residential Fire Installations the minimum Bell Time out is 5 minutes Temporal Three Fire Signal shall be enabled Refer to sectio...

Страница 52: ...ption 6 Audible Exit Fault Enable OFF 168 21 SetClockForward DaylightSaving Month 009 Week 005 169 21 SetClockBack StandardTime Month 004 Hour 003 320 22 Alarm Reporting Codes Zones 01 08 11 329 23 Pr...

Страница 53: ...estart Enabled Exit Delay Restart Disabled ON 023 19 Tenth System Options Option 5 Switching from Away to Stay Disabled Away to Stay Toggle Option Permitted ON 101 108 20 Zone Attributes Defaults 01 0...

Страница 54: ...Supervisory Restore 33 347 24 Misc Maintenance Reporting Codes Telephone 1 2 FTC Restore 54 DLS Lead in and Lead out FF General Zone Fault Alarm 80 General Zone Fault Restore 80 Delinquency Reporting...

Страница 55: ...Buzzer Follows Bell Disabled ON 168 21 Daylight Savings Time Begins Month 004 Week 001 169 21 Daylight Savings Time Ends Month 010 Week 005 328 22 Miscellaneous Alarm Reporting Codes Recent Closing 00...

Страница 56: ...WV DQG RWKHU UHOHYDQW SURYLVLRQV RI LUHFWLYH 7KH FRPSOHWH 5 77 HFODUDWLRQ RI RQIRUPLW FDQ EH IRXQG DW KWWS ZZZ GVF FRP OLVWLQJVBLQGH DVS 6 MDNR Y UREFH SURKOD XMH H WHQWR Y UREHN MH Y VRXODGX VH Y HPL...

Отзывы: