PC1404 Wiring Diagram
200–350 mA
85
1404
-31X
2-WIRE SMOKE DETECTORS
For NA
installations
only
4.0/7.0 Ah
LCD5511
LED5511
PC1555RKZ
PK5500/PK5501
PK5508/PK5516
PC1404RKZ
US: F53AL01BPC1404
IC:160A-PC1404
(NA)
(EU)
FUSE 315mA/250V
(within terminal block)
ZONE DOUBLING
1500
BROWN
GREEN
RED
GOLD
2400
RED
YELLOW
RED
GOLD
-
-
2200 Ohm
END-OF-LINE
RESISTOR
EOLR-3
RM-1/RM-2 POWER LOOP
SUPERVISORY RELAY
EOLR-2
END-OF-LINE
RESISTOR
5600 Ohm, 0.5W
ALARM
INITIATING
LOOP
RESISTANCE
100 Ohm
12V
DC
o
.
is UL listed
-
WARNING: Incorrect connection of batteries may result in battery rupture or
fire hazard. Do NOT allow metal objects to connect the positive and
negative terminals. Ensure that batteries are connected with correct polarity
[Red to (+), Black to (-)]. Failure to comply with this may result in battery
rupture and/or fire hazard.
30
CON1
BAT+BAT-
RED
BLK
so s
I
-49
(32 120 F)
Use a UL/CSA-listed Class 2 Transformer
16.5V
AC
40 VA DSC PTD 1640U (USA)/
PTD 1640 (CDN).
D
O
not connect transformer to
receptacle controlled by a switch.
T-1
R-1
TIP
RING
RJ-31X
RED
GRN
BRN
GRA
Telephone line wiring
UL
For EU
installations
only
REFER TO
MANUAL FOR
LIST OF
COMPATIBLE
DEVICES
4-WIRE SMOKE DETECTORS
0
-
(for UL/ULC applications)
Refer to the
Installation Guide (29008503)
and
User Manual (29008622)
for complete
operating instructions.
In Canada, the PC1404 is listed for Residential Fire and Burglary installations. The product
shall be installed as per UL-S540 and ULC-S310 Standards.
26 AWG
AUX Wiring
Use No. 14-22 AWG conductor.
Total current draw from keypads,
PGM outputs and AUX circuits must
not exceed 550mA.
SIA-FAR Minimum System
Requirements:
1 PC1404 Panel
1 Local annunciation devices
Local annunciation devices may be
any combination of these keypads:
PK5500, PK5501, PK5508, PK5516,
PC1404RKZ, LCD5511, LED5511Z,
PC1555RKZ
Battery capacity for 4 h standby is
at least 4 Ah. Battery capacity for 24 h
standby is 7 Ah. (Max. Aux current shall
be in accordance with Section 2.2 battery
connection.) Recommended batteries:
DSC BD4-12 or DSC BD7-12.
PC14-1
24
13.7
FSA-210B Series
NOTE
:
Refer to the FSA-210 Installation Manual for more details.
NAME
MODEL
MAX #
BASE
COMPATIBILITY ID
DSC
NONE
FS200
SEE NOTE
Applicable UL Standards
UL 985 Household Fire Warning System Units
UL1023 Household Burglar Alarm System Units
UL 1635 Digital Alarm Communicator System Units
ANSI/SIA CP-01-2010
(a) The delay (power-up) time marked on the installation wiring diagram of the smoke detector
or on the installed smoke detector(s) is to be used. Control panel is suitable for the following
UL installations:
Installation Type
Signalling Means
Resi Fire Burg
DACT
Note: It is the installer’s responsibility to
ensure that the external PRIMARY wires
are tied together using a cable tie or
equivalent as close as possible
to the terminal block.
UL compatibility ID for FSA-210B
series is FS200; for ULC listed
installations, use FSA-210A and
FSA-410A series.
Test the alarm system at least
once per week.
THIS UNIT INCLUDES AN ALARM VERIFICATION FEATURE THAT WILL RESULT IN A
DELAY OF THE SYSTEM ALARM SIGNAL FROM THE INDICATED CIRCUITS. THE
TOTAL DELAY (CONTROL UNIT PLUS SMOKE DETECTORS) SHALL NOT EXCEED 60
SECONDS. NO OTHER SMOKE DETECTOR SHALL BE CONNECTED TO THESE
CIRCUITS UNLESS APPROVED BY THE LOCAL AUTHORITY HAVING JURISDICTION.
Note: Alarm Verification is not supported for 2-wire interface, only 4-wire.
.
230/240 VAC
50/60Hz